Precision Digital PD650 User Manual
Page 50

Model PD650 Large Display Process Meter
Instruction Manual
50
Rate or Total, Latching or Non-Latching Relays
Note
To simplify programming, write down the desired programming
values prior to attempting to program the meter. The Programmed
Parameter Settings form located at the back of this manual provides
a convenient method to record the user settings; it also provides the
factory setting for most of the programmable parameters.
Press ENTER, then press ENTER again when the
setup (Setup) function appears
Setup
To set up set points
Set point 1 (SEt 1) will be displayed. Press ENTER to
program set point 1 or wait and the display will move to the
next set point. When set point 4 (SEt 4) is shown, the meter
will exit the setup (Setup) menu and move to the next
programming function.
SEt 1
then
SEt 2
then
SEt 3
then
SEt 4
then
I or E
If ENTER is pressed while set point 1 (SEt 1) is
shown, the display will then show rate or total
(r or t) flashing alternately.
Select the desired one by pressing ENTER when
it is flashing.
SEt 1
then
R or t
Select process/rate
After selecting r for process/rate, the display will show latch
(LatCH). Press ENTER to program this function. If ENTER is
not pressed within 3 seconds, this function will remain
programmed as it was before, and the next set point will be
displayed.
R or t
then
LatCk
then
SEt 2
If ENTER is pressed while the display reads
LatCH, yes or no (Y or N) will flash alternately. To
program this set point for Latching relay, press
ENTER when Y is flashing. To program this set
point for non-latching relay, press ENTER when n
is flashing. After making the selection, setup of set
point 1 is complete and the next set point will be
displayed. Press ENTER to set up that set point, if
not, wait until desired set point is displayed or wait
for the meter to exit the Setup menu completely.
R or t
then
LAtCH
then
y or n
then
SEt 2