FAIL-SAFE 
OPERATION 
Relay coils are energized in non-alarm condition. In case of 
power failure, relays will go to alarm state. Fail-safe operation 
may be disabled, by removing jumper J5 located on the 
Options Board. 
AUTO 
INITIALIZATION 
When power is applied, relays assigned to total will reflect the 
state of the accumulated total value in memory. Relays 
assigned to process/rate will reflect the state of the input to the 
meter. 
RELAYS RESET
Total relays reset
1.
When total is reset to zero, if set up for external total reset
2.
After delay has elapsed, if set up for internal total reset
3.
Manual any time, if set up for external total reset (via user 
supplied external contact closure at terminals AK and CM 
or front panel ACK button) 
Note: Manual reset resets all manually resettable relays.
Process/rate
relays reset
1.
Automatic reset only
2.
Manual reset only, at any time
3.
Automatic plus manual reset at any time
4.
Manual reset only after alarm condition has been 
corrected 
Automatic reset: Relays will automatically reset when the 
input passes the reset point. 
Manual reset: It can be performed via user supplied external 
contact closure at terminals AK and CM or front panel ACK 
button. Manual reset resets all manually resettable relays. 