beautypg.com

Precision Digital PD650 User Manual

Page 46

background image

Model PD650 Large Display Process Meter

Instruction Manual

46

Set Alternating Total/Rate Display

The display may be programmed to automatically toggle between rate and total
every ten seconds. To set up the alternating display select no (n) for both, display
rate (dSPy r) and display total (dSPy t) under Display Selection (

dsplay

).

Set alternating total and rate display

Press ENTER, then press it again when display
(dsplay) function appears.

Dsplay

Press ENTER when display rate (DSPY r) appears

DSPY r

Yes or no (Y or n) will flash alternately. Press ENTER when
n appears.

Y or n

Press ENTER when display total (DSPY t) appears

DSPY t

Yes or no (Y or n) will flash alternately. Press ENTER when
n appears.

Y or n

Note: Selections made through the display menu (dSPLAY) can be made with
or without the lockout jumper installed, but only become active when the
lockout jumper is installed.

This completes calibration and setup of the Basic Meter and
Totalizer.

Parameter Combinations Resulting in Error Message

(error1 )

Certain extreme combinations of parameter selections may exceed the totalizer
range of the meter. If this occurs, the meter will momentarily display Error 1
immediately after a programming operation. Steps to correct this situation are:
Increase the number of decimal places in rate or totalizer conversion factor.

or

Decrease the number of decimal places in total.

or

Increase the time base from Second to Minute, Minute to Hour, or Hour to Day.