User di 1, Do 8, Do 1 – Precision Digital PD6200 User Manual
Page 81: Di 8, Programmable function keys user menu ( user )

Model PD6200 Analog Input Rate/Totalizer
Instruction Manual
81
Programmable Function Keys User Menu (user)
The User menu allows the user to assign the front panel function keys 
F1, F2, F3 and up to eight digital inputs to access most of the menus or 
to activate functions immediately (e.g. Reset max & min). Up to eight 
digital outputs can be assigned to a number of actions and functions 
executed by the meter (e.g. Alarms, relay acknowledgement, etc.). 
 user
 
 dI 1
 
user
 dO 8
 
user
 dO 1
 
user
 dI 8
 
user
 F1
 
user
 F3
 
user
 F2
 
user
Function Keys & Digital I/O Available Settings
Display Description
Display Description
AcH
Acknowledge relays
Big HL
Max/min big display
Rst Hi
Reset max
Lit Hi
Max on little display
Rst Lo
Reset min
Lit Lo
Min on little display
Rst HL
Reset max & min
Lit HL
Max/min little display
C tare
Capture tare
disabl
Disable function key
Tarest
Reset tare
menu
Menu button
relay
Relay menu
Right
Right arrow button/F1
Set 1
Set point 1 - 8
up
Up arrow button/F2
Rly d
Disable all relays
Enter
Enter button/F3
Rly E
Enable all relays
Alm 1
Alarm 1 – 8
O Hold
Relays & output hold
F On 1
Force relay 1 on
d Hold
Display hold
F On 2
Force relay 2 on
Big Hi
Max on big display
F On 3
Force relay 3 on
Big Lo
Min on big display
F On 4
Force relay 4 on