Baud, Slavid, Tr dly – Precision Digital PD6200 User Manual
Page 76: Serial t-byt, Parity

Model PD6200 Analog Input Rate/Totalizer
Instruction Manual
76
Modbus RTU Serial Communications (serial)
The meter is equipped with serial communications capability as a stan-
dard feature using Modbus RTU Serial Communication Protocol. 
To communicate with a computer or other data terminal equipment, an 
RS-232 or RS-422/485 adapter option is required; see Ordering Informa-
tion
on page 7 for details.
Warning!
Do not connect any equipment other than Precision 
Digital’s expansion modules, cables, or meters to the 
RJ45 M-LINK connector. Otherwise damage will occur 
to the equipment and the meter. 
Note: More detailed instructions are provided with each optional serial
communications adapter.
Note: Refer to the P
RO
V
U
®
Modbus Register Tables located at
www.predig.com for details.
 baud
 
Serial
 SlavId
 
Serial
 tr dly
 
Serial
serial
 t-byt
 
Serial
 Parity
 
Serial
When using more than one meter in a multi-drop mode, each meter must 
be provided with its own unique address. The meter address (Slave ID) 
may be programmed between 1 and 247. The transmit delay may be set 
between 0 and 199 ms. The parity can be set to even, odd, or none with 
1 or 2 stop bits. 
The PD6200 can also be connected to another PD6200 with a special 
PDA1200 cable, allowing the user to copy all the settings from one meter 
to another, using the Copy function. 
