Modbus
®
RTU Serial Communications
SLAVE ID
1 – 247 (Meter address)
BAUD RATE
300 - 19,200 bps
TRANSMIT 
TIME DELAY 
Programmable between 0 and 199 ms 
or transmitter always on for RS-422 communication 
DATA
8 bit (1 start bit, 1 or 2 stop bits)
PARITY
Even, Odd, or None with 1 or 2 stop bits
BYTE-TO-BYTE 
TIMEOUT 
0.01 – 2.54 second
TURN AROUND 
DELAY 
Less than 2 ms (fixed)
Note: Refer to the P
RO
V
U
®
Modbus Register Tables located at www.predig.com
for details.
PDA1044 Digital Input & Output Expansion Module
CHANNELS
4 digital inputs & 4 digital outputs per module
SYSTEM
Up to 2 modules for a total of 8 inputs & 8 outputs
DIGITAL INPUT 
LOGIC HIGH 
3 to 5 VDC
DIGITAL INPUT 
LOGIC LOW 
0 to 1.25 VDC
DIGITAL OUTPUT 
LOGIC HIGH 
3.1 to 3.3 VDC
DIGITAL OUTPUT 
LOGIC LOW 
0 to 0.4 VDC
SOURCE 
CURRENT 
10 mA maximum output current
SINK 
CURRENT 
1.5 mA minimum input current
+5 V 
TERMINAL 
To be used as pull-up for digital inputs only 
Connect normally open pushbuttons across +5 V & DI 1-4. 