Isolated 4-20 ma transmitter output – Precision Digital PD6200 User Manual
Page 12

Model PD6200 Analog Input Rate/Totalizer
Instruction Manual
12
TIME DELAY
0 to 999.9 seconds, on & off relay time delays 
Programmable and independent for each relay. 
FAIL-SAFE 
OPERATION 
Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition.
In case of power failure, relay will go to alarm state.
AUTO 
INITIALIZATION 
When power is applied to the meter, relays will reflect the 
state of the input to the meter. 
Isolated 4-20 mA Transmitter Output
OUTPUT 
SOURCE 
Rate/process, total, grand total, max, min, set points 1-8, or 
manual control mode 
SCALING RANGE 1.000 to 23.000 mA for any display range.
CALIBRATION
Factory calibrated: 4.000 to 20.000 = 4-20 mA output
ANALOG OUT 
PROGRAMMING 
23.000 mA maximum for all parameters: 
Overrange, underrange, max, min, and break 
ACCURACY
± 0.1% FS ± 0.004 mA
TEMPERATURE 
DRIFT 
0.4 µA/
C max from 0 to 65C ambient,
0.8 µA/
C max from -40 to 0C ambient
Note: Analog output drift is separate from input drift.
ISOLATED 
TRANSMITTER 
POWER SUPPLY 
Terminals I+ & R: 24 VDC
 5% @ 40 mA maximum; may
be used to power the 4-20 mA output or other devices. 
Refer to Figure 6 on page 20 and Figure 14 on page 24. 
EXTERNAL LOOP 
POWER SUPPLY 
35 VDC maximum
OUTPUT LOOP 
RESISTANCE 
Power supply
Minimum
Maximum
24 VDC
10
 700
35 VDC (external)
100
 1200