beautypg.com

Precision Digital PD6200 User Manual

Page 73

background image

Model PD6200 Analog Input Rate/Totalizer

Instruction Manual

73

Display Parameter Action/Setting

O-rang

Overrange

Program mA output for display overrange

u-rang

Underrange

Program mA output for display underrange

Break

Loop Break

Set relay condition if loop break detected

Force

Force

Force analog output value for loop break

Ignore

Ignore

Ignore loop break condition

mAx

Maximum

Program maximum mA output allowed

min

Minimum

Program minimum mA output allowed

Calib

Calibrate

Calibrate 4-20 mA output (internal refer-
ence source used for scaling the output)

4 mA

4 mA output

Enter mA output value read by milliamp
meter with at least 0.001 mA resolution

20 mA

20 mA output

Enter mA output value read by milliamp
meter with at least 0.001 mA resolution

user

User I/O

Assign function keys and digital I/O

F1

F1 function key

Assign F1 function key

F2

F2 function key

Assign F2 function key

F3

F3 function key

Assign F3 function key

dI I

Digital input 1

Assign digital input 1 – 8, if expansion
modules are connected

dO 1

Digital output 1

Assign digital output 1 – 8, if expansion
modules are connected

ICal

Internal source
calibration

Enter internal source calibration (used for
scaling the meter without a signal source

C CAL

Current
calibration

Calibrating 4-20 mA current input (internal
reference source used for scaling the input)

C lo

Current low

Calibrate low current input (e.g. 4 mA)

C Hi

Current high

Calibrate high current input (e.g. 20 mA)

v CAL

Voltage
calibration

Calibrating voltage input

v Lo

Voltage low

Calibrate low voltage input (e.g. 0 V)

v Hi

Voltage high

Calibrate high voltage input (e.g. 10 V)

Copy

Copy

Enter copy function

send

Send

Send meter settings to another meter

This manual is related to the following products: