Precision Digital PD6200 User Manual
Page 67
![background image](https://www.manualsdir.com/files/858245/content/doc067.png)
Model PD6200 Analog Input Rate/Totalizer
Instruction Manual
67
Scaling the 4-20 mA Analog Output (Aout)
The 4-20 mA analog output can be scaled to provide a 4-20 mA signal
for any display range selected.
No equipment is needed to scale the analog output; simply program the
display values to the corresponding mA output signal.
The Analog Output menu is used to program the 4-20 mA output based
on display values.
Aout
setup
dis 1
Aout
0
04.000
d i s 1
dis 2
Aout
0
20.000
d i s 2
Out 1
Aout
0
4.000
O u t 1
Out 2
Aout
2
0.000
O u t 2
For instructions on how to program
numeric values see Setting Numer-
ic Values, page 34.