Basic comfort air kit
Technical dept. - All rights reserved by MCZ Group S.p.A. - Reproduction prohibited
2.2.2. Replacing the fan
CAUTION!
CUT OFF THE 230 V SUPPLY BY DISCONNECTING THE
CONTROL UNIT FROM THE MAINS.
Lift the flap
If the control unit is seated in the fan kit, remove the fixing
screws and disconnect the various electrical connections.
Loosen the 4 screws “P” (two to the left and two to the right)
and remove the panel to gain access to the fan
Remove the rubber sleeve “Q”
Remove the screw “R” at the front and the screw at the rear
“S” opposite the fixing bracket
Remove the fan connection faston connector
now the fan can be removed and replaced
CAUTION!
MAKE SURE YOU SECURE ALL WIRES WHEN YOU
DISCONNECT THEM.
YOU WILL BE UNABLE TO RETRIEVE THEM IF THEY
FALL INTO THE CLADDING.
Important!
All electrical connections must be made by qualified
staff in accordance with the applicable Laws in force in
all countries, using suitable equipment and according
to the diagram provided in this manual. All operations
must be performed with the 230V 50 Hz mains power
supply cable disconnected.
Mcz will not be held liable for personal or property
damage due to incorrect connections or improper
device use.