NetScanner™ System (9016, 9021, & 9022) User’s Manual

ii

dd

Description

‘q’ read

index

www.PressureSystems.com

3 - 72

15

00
01
02
03

(for Models 9021 and 9022 only; reserved for 9016)
Set Amplifier Gain to 5000 mV FS Range (G=1) (default)
Set Amplifier Gain to 250 mV FS Range (G=20)
Set Amplifier Gain to 100 mV Range (G=45)
Set Amplifier Gain to 50 mV FS Range (G=90)

16

00

01

Disable Host Response/Stream Total Size Prefix
(default).
Enable Host Response/Stream Total Size Prefix (2-byte
big-endian binary value with total size of response or
stream data in bytes that follows it).

08

17

00

Set TCP Connect Port per eeee as decimal value
(default=9000).

09

18

00
01

Disable Auto UDP Broadcast at Reset (default).
Enable Auto UDP Broadcast at Reset.

0A

19

00

01

Set Minimum Temperature Alarm Set Point (in

N

C)

per eeee as decimal value (default = 0

N

C).

Set Maximum Temperature Alarm Set Point ( in

N

C)

per eeee as decimal value (default = 60

N

C).

0D

0E

1B

00

Set Thermal Update Scan Interval per eeee as decimal
value (seconds), 1 <= eeee <= 3600 seconds (default = 15).

11

22

00

(9022 ONLY) Set Front-end Automatic Calibration
Interval
. 5 <=eeee <=3600 seconds (default=60); 0=turn
off calibration.

12

23

--

(9022 ONLY) Calculate Front-end Calibration
Coefficients Immediately
.

25

00

(for Models 9021 and 9022 ONLY) Set Generic Sensor
Parameters to Default.
(Offset term=0.0; Gain term=1.0;
c0=0.0; c1=1.0; c2=0.0; c3=0.0; user-defined date=0;
manufacturing reference number=0; full-scale range
code=0; front end gain=0 (unity))