beautypg.com

Hook-up, Assembly 5. preparation & use, Air supply – Sealey SM224 User Manual

Page 2

background image

3. ASSEMBLY

5. PREPARATION & USE

As you unpack the product, check contents. Should

there be any damaged or missing parts contact

your supplier immediately.

3.1. Assemble the gate valve (A) which

connects the tank to the reservoir, directly

to the reservoir as shown in fig.1, ensuring

that a rubber seal is fitted to both ends of

the valve.

3.2

Screw the air regulator and safety valve

assembly (B) to the reservoir as shown in

fig.2 ensuring that the rubber seal

provided is in place.

3.3

Assemble the two upper tank support

arms (C) into the sockets provided on the

tank but do not tighten the fittings yet.

3.4

Place the upper tank onto the support arms

and lower it down until the tank outlet

drops into the top of the gate valve (A). Fix

the tank to the valve by tightening ring (Q)

as shown in fig.4. Tighten the hex socket

bolts at either end of the upper tank

supports (C). Fit handle into support arm

brackets (C) and tighten.

3.5

Mount the cleaning brush in its stowage

position on the underside of the lid over to

the left hand side. Feed the brush tube (T)

through the hole in the righthand side of

the tank and connect it to outlet (R) on the

head of the regulator /safety valve

assembly.

5.1

Filling the unit with cleaning fluid.

5.1.1 Make sure that the drain cock at the base

of the unit is closed as shown at (F) in fig.6.

5.1.2 Turn the lever (D) to the right which is the

air discharge position. This allows the fluid

to drain more easily out of the upper tank

and into the lower reservoir. See fig.7.

Open the gate valve (E) by turning the

lever to the vertical position.

5.1.3 Shut the pressure regulator by pulling and

turning the pressure regulator knob (G)

anticlockwise. See fig.8.

5.1.4 Pour cleaning fluid into the upper tank and

allow it to drain down into the lower

reservoir. Continue to fill the unit until the

level has risen to the maximum mark on

the level indicator tube.

5.1.5 Before using the unit ensure that all filter

grids are in place.

WARNING! Wear approved safety eye

protection, mask and gloves. If solvent gets on

skin or in eyes wash thoroughly with water and

take any other action as required by the solvent

instructions.

4.1.

Ensure that the air regulator valve is closed before connecting the air supply.

4.2.

An air pressure of 40-60psi and an available air volume of 6cfm will be required to operate the unit.

WARNING! Ensure air supply is clean and does not exceed 110psi. Too high an air pressure and/or unclean air will

shorten the product life, and may be dangerous, causing possible damage and/or personal injury.

Air supply must be equipped with regulator & water trap.

4.3.

Drain the air supply tank daily. Water in the air line will damage the unit.

4.4.

Clean the air supply filter weekly. For recommended hook-up, see

diagram to right.

4.5.

Line pressure should be increased to compensate for unusually long

air hoses (over 8 metres). The minimum hose internal diameter

should be 10mm and fittings must have the same internal

dimension.

4.6.

Keep hose away from heat, oil and sharp edges. Check hoses

for wear, and make certain that all connections are secure.

4.7.

The air inlet connection is 1/4”BSP.

4. AIR SUPPLY

HOOK-UP

Original Language Version

SM224 Issue: 3(SP) - 04/09/13

© Jack Sealey Limited