Emerson E2 User Manual
Page 233

Appendix C: Alarm Advisory Messages
•
C
-
11
Normal Low Limit Exceeded
User
An analog value has fallen below its programmed Lo
Limit setpoint.
Not Enough Backed Memory
10
The E2 tried to save data to the battery-backed mem-
ory, but the memory was full.
Not Enough Flash Memory
20
The E2 tried to save data to the flash memory, but the
memory was full.
Not Enough Memory
10
The E2 tried to save data to unbacked memory, but
the memory was full.
Not Enough Scatch Pad Memory
50
The E2 tried to save data to the scratch pad memory,
but the memory was full.
Notice Limit Exceeded
User
An analog sensor’s programmed notice limit has
been exceeded.
Num. Of Events Exceeded Limit
User
A digital value has transitioned ON more times than
its defined Number of Events setpoint.
Occupied Hi Limit Exceeded
User
An analog value has risen above its defined high limit
setpoint during OCCUPIED mode.
Occupied Low Limit Exceeded
User
An analog value has fallen below its defined low
limit setpoint during the OCCUPIED mode.
Off Time Exceeded Limit
User
A digital value has been OFF longer than its defined
Time Off Last setpoint.
Oil Failure Occurred
User
An oil sensor for a compressor has detected a failure.
On Time Exceeded Limit
User
A digital value has been ON longer than its defined
Time On Last setpoint.
Open Wire
30
MultiFlex ESR controller has detected an open wire
on the valve input.
Overcurrent
30
MultiFlex ESR controller has detected an overcurrent
condition on the valve.
Override Log lost - CRC Error
20
An internal error in the E2 has resulted in a loss of the
override log.
Override Lost Output Cleared
20
A user tried to override an output on a CC-100, RT-
100, or similar Echelon device, but the override was
not performed successfully. Try the override com-
mand again. If this alarm persists, call Retail Solu-
tions service.
Override Operation Didn't Take
20
The E2 tried to carry out an override and was unsuc-
cessful.
Override State Not Restored
50
An overridden input or output has remained in the
override state longer than its programmed time.
Pad Memory Corrupted - Reboot
30
A problem with memory has resulted in a reset of the
E2.
Part Cnfg Loss-Ptr
15
Due to an internal error, part of E2’s configuration
data has been lost.
Alarm Name
Default
Priority
Definition