beautypg.com

Intelligent pre-starts and pre-stops, 11 separate setpoints, 12 ahu zone control – Emerson E2 User Manual

Page 166: 13 hardware overview

background image

11-24

E2 RX/BX/CX I&O Manual

026-1610 Rev 13 14-SEP-2011

comfortably within the range of the new setpoint.

Figure 11-15 shows an example of how pre-starts and

pre-stops work in a heating application. From unoccupied
mode, the pre-start period ramps the temperature up
slowly so that when the scheduled change from unoccu-
pied to occupied mode occurs, the temperature will
already be at or near the occupied heating setpoint. During
the pre-stop, which occurs before AHU Control goes from
occupied to unoccupied mode, heating is suspended and
the temperature is allowed to “coast” down to the unoccu-
pied setpoint.

Intelligent Pre-Starts and Pre-Stops

OSS is designed to handle pre-starts and pre-stops in

the most energy-efficient manner possible. Every time a
pre-start or pre-stop occurs, OSS measures the amount of
time it takes to bring the temperature from the previous
setpoint to within the “comfort zone” of the new setpoint
(a user-defined range of values above and below the set-
point within which the temperature is considered accept-
able). This duration is used to determine the average rate
of temperature change, called the K factor.

The K factor is stored in the memory along with the

average value of the outdoor air temperature during the
pre-start or pre-stop. Over time, collected K factor data
will be sorted and combined into a table. As a result, by
constantly observing and recording the results of previous
pre-starts and pre-stops, OSS will be able to intelligently
guess how much time a pre-start or pre-stop mode should
last based on the outside temperature.

AHU Control keeps track of three different kinds of K

factors:

Heat K factor - used to guess pre-start dura-

tions for AHUs operating in heating mode.

Cool K factor - used to guess pre-start dura-

tions for AHUs operating in cooling mode.

Coast K factor - a measurement of the

change in temperature when no heating or
cooling is active. This is used to determine
pre-stop durations for both heating and cool-
ing AHUs.

11.6.11 Separate Setpoints

The Separate Setpoints strategy for AHU allows a Cut

In/Cut Out setpoint to be set up for each heat and cool
stage instead of just one cool and one heat setpoint set up
for each stage (Normal strategy). Dehumidification con-
trol can be performed while controlling with separate set-
points.

11.6.12 AHU Zone Control

Unlike MultiFlex RTU rooftop controller applications,

AHU applications are not required to be grouped into
Zone applications (AHUs are usually large enough to be
“zones” in and of themselves).

However, if desired, you may associate an AHU Con-

trol application with a Zone application. The AHU will
then use the Zone’s Temperature Control setpoints, occu-
pancy state, summer/winter state, and economization and
dehumidification enable signals. More information on
Zone control is available in Section 11.7, Zone Control.

11.6.13 Hardware Overview

To set up an AHU for control by an E2, numerous tem-

perature and humidity sensors for several different appli-
cations must be connected to the I/O Network, as well as
fan and cool proof checking devices, economization
checking devices, curtailment devices, and all of the heat-
ing, cooling, and dehumidification outputs.

Listed below are wiring instructions for some of the

inputs and outputs that are part of a typical AHU setup.

Figure 11-15

- Diagram of Pre-Start and Pre-Stop Operation

OCCUPIED
SET POINT

UNOCCUPIED

SET POINT

UNOC

C

U

PIED

UNOC

C

U

PIED

PRE-ST

ART

OCC

U

PIED

PRE-ST

OP

(COAST)

26512036

Inputs

Sensor Type

Wiring

Instructions

Space Temperature

Temperature

See Table 9-1 on
page 9-3

Space Humidity

Humidity

See Table 9-1 on
page 9-3

Supply Air Temp

Temperature

See Table 9-1 on
page 9-3

Return Air Temp

Temperature

See Table 9-1 on
page 9-3

Outdoor Air Temp

Temperature

Set up as Out-
door Air Provider
in Global Data
(see

Section

10.17

).

Table 11-10

- Suction Group Inputs