Installation – Enviro Kodiak 1200 Insert User Manual

Page 33

background image

33

At least

3 feet (914 mm)

Hearthpad

Floor

Pedestal

Woodstove

Optional

fan

Outside air connection

through wall or floor

Double wall pipe

Ceiling support

Ceiling

Spark arrestor cap

Roof flashing

Roof

Radiation Shield

Insulated

chimney

Bolt stove to floor

Figure 33: Freestanding installation into mobile home.

The pedestal must be firmly bolted to the floor using two (2) 1⁄4” bolts. Be sure to replace any insulation

or panels removed when fastening the bottom nuts.
If room air starvation occurs because the air intake is blocked with ice, leaves etc. or because the stove

door was left open, or due to a strong exhaust fan operating, dangerous fumes could be sucked into the

room.
IN SOME AREAS IT MAY BE REQUIRED TO ELECTRICALLY GROUND THE STOVE TO THE STEEL CHASSIS

OF THE MOBILE HOME.
When this unit is installed in a Mobile Home it must be grounded to the steel chassis or connected to a

grounding rod.
Manufactured (Mobile) home installation must be in accordance with the Manufactured Home Construction

and Safety Standard, UL 307B, Title 24 CFR, Part 3280 and/or The Standard for Manufactured Home

Installations, ANSI A225.1/NFPA 501A.

WARNING: DO NOT INSTALL IN A MOBILE HOME SLEEPING ROOM.

These connectors must be installed in accordance

with the manufacturer’s instructions. Use only

specified components. The chimney and pipe must

extend at least 10 feet (2.4 m) above the stove and

3 feet (0.9 m) above the highest point of the roof.

Install a rain cap with spark arrestor at the top that

will not impede the smoke exhaust. The chimney

must be supported at the ceiling or roof so that its

weight will not sit on the stove. Seal with silicone to

maintain vapor barrier at the chimney and outside

air penetrations.
CAUTION: THE STRUCTURAL INTEGRITY

OF THE MOBILE HOME FLOOR, WALL, AND

CEILING/ROOF MUST BE MAINTAINED.
OUTSIDE AIR :
Connection from the stoves air intake to the

outside is mandatory, (MOBILE HOMES ONLY)

either through a hole in the wall not higher than

the stoves bottom or through a hole in the floor

beneath the pedestal, using the fresh air adaptor

provided. If the air intake is through the floor, the

hole in the pedestal back must be closed with the

sheet metal cover provided. Avoid cutting any floor

joists, wall studs, electrical wiring or plumbing.

Seal around the outside air pipe with insulation to

prevent drafts. Also install a 1⁄4” mesh rodent or

pest screen in the end of fresh-air pipe. Fresh-air

connection must be of a non-combustible material,

example: 4” (10.16 cm) flexible aluminum single

wall pipe.
Fresh air could also be supplied from a vented

crawlspace.

Installation