Initial Installation

24" (610mm)

Maximum

Horizontal

24" (610mm)

Minimum

Vertical

Inside

Finished

Collar

Wall

Thimble

Horizontal

Vent

Termination

Exterior

Wall Surface

Insulation

Interior Wall

Surface

If installed on a

carpeted surface

a hearth is required

Interior

Wall Surface

2.5"

(64mm)

Inside

Finished

Collar

Horizontal

Vent Section

Exterior

Wall Surface

Horizontal

Vent

Termination

Wall

Thimble

Insulation

If installed on a

carpeted surface

a hearth is required

NOTES:
(1)
The horizontal run of vent pipe must be

level and should have a 1⁄4 inch rise

for every one foot of run towards

the termination. Never allow the

vent to run downward. This could cause

high temperature and may present the

possibility of a fire.

(2) The location of the horizontal vent

termination on the exterior wall must not

be easily blocked or obstructed. Refer to

“Initial Installation - Vent Termination

Restrictions” section.

(3) When installing a vent pipe in a chase

the minimum clearance to combustibles

is 2” (51 mm).

NOTE: Vent pipe must not be longer

than 18” (457 mm) maximum when

installing straight through exterior wall.

Maintain manufacturer’s clearances to

combustibles with venting.
Vent may extend between 6 inches (152

mm) and 18 inches (457 mm) maximum

straight out.

When installing this unit in a corner the

maximum distance after 45˚ elbow is 9

inches (228 mm).
If between 9 inches (229 mm) and 24

inches (610 mm), a 14 inches (356 mm)

snorkel must be used.

16

Figure 17: Straight Through Wall Installation.

Figure 18: Up Then Through Wall Installation.