beautypg.com

2 configuration parameters, 1 hart tag, Configuration parameters 7.2.1 – Emerson IFT9701 User Manual

Page 54: Hart tag

background image

46

Model IFT9701 Transmitter Instruction Manual

Configuration with ProLink II Software

continued

7.2

Configuration parameters

Use the Configuration window to perform the following tasks:

Assigning a HART tag to the flowmeter

Changing process variable measurement:

-

Changing measurement units for the mass flow or volume flow rate

-

Changing the flow cutoff value

-

Changing the internal damping value

-

Changing the flow direction parameter

Setting range values for the milliamp output

Scaling the pulse output

7.2.1

HART tag

The HART tag consists of up to eight characters that identify the flowmeter when it communicates
with other devices in a HART multidrop network.

To assign a HART tag to a flowmeter:

1. From the ProLink menu, click on Configuration.

2. In the Configuration window, click on the Device tab.

3. When the Device panel appears (as depicted in Figure 7-1), enter the desired tag of up to eight

characters, then click on OK. The tag can include spaces and periods.

Figure 7-1

Configuration window – Device panel