Power Supply and Output Wiring
continued
Ge
tti
n
g
Sta
rted
P
o
wer
Su
pp
ly
an
d O
u
tp
ut Wi
ri
ng
Mounting the
Remo
te T
ransmitter
Be
fo
re
Y
o
u
Begin
Figure 4-8
Wiring to Series 3000 applications platform with I/O cable
Figure 4-9
Wiring to Series 3000 applications platform with screw-type or solder-tail terminals
Figure 4-10 Wiring to field-mount Series 3000 applications platform
(1) Paired cables with shield. Maximum length is 50 feet for 28 AWG wire (15 meters for 0,1 mm² wire),
500 feet for 22 AWG wire (150 meters for 0,3 mm
2
wire).
(2) Do not connect shields at this end.
IFT9701 pulse
output terminals
Series 3000 I/O cable
terminals
See Note 2
Earth
ground
(1) Paired cables with shield. Maximum length is 50 feet for
28 AWG wire (15 meters for 0,1 mm² wire), 500 feet for 22 AWG
wire (150 meters for 0,3 mm
2
wire).
(2) Do not connect shields at this end.
IFT9701 pulse
output terminals
Series 3000 screw-type or
solder-tail terminals
See Note 2
Earth
ground
(1) Paired cables with shield. Maximum length is 50 feet for 28 AWG wire (15 meters for 0,1 mm² wire),
500 feet for 22 AWG wire (150 meters for 0,3 mm
2
wire).
(2) Do not connect shields at this end.
IFT9701 pulse
output terminals
Series 3000 field-mount
terminals
See Note 2
Earth
ground