External Optional Cabinets

53

EXT-Maint X3-1&2 on UPS Parallel Board M3 (leave open if no external bypass switch is used). Pro-

vides external maintenance bypass interlock protection for the UPS. Short circuit means external

bypass closed.
EXT-Out (X3-3&4) on UPS Parallel Board (leave shorted if no external output switch is used). Pro-

vides external output interlock protection for paralleled UPS modules. Short circuit means external

output switch closed.

4.3

Isolation Transformer Option

Isolation transformers are required in cases requiring galvanic isolation between the input supply

mains and the UPS.
These options are housed in cabinets and they are available for every range of UPS.
These optional cabinets provide the Top Cable entry function.

Figure 36 Equipment arrangement—UPS, battery cabinet and top-entry Isolation Transformer Cabinet

Figure 37 Single input external isolation transformer cabinet

NOTE
Terminals and cabling for the battery connection is not a part of the MBP or TC cabinet.

TCE

TX

UPS

BATTERY

cabinet

FRONT

Q1

Q3

Q5

X3

X1

CB

To Load

UPS

N

Bypass

Supply

Input Mains Supply

3P

Supplied by

Others

Isolation Transformer Cabinets

T1

QF1

Q2