UPS Multi-Module Installation

50

3.4

Dual Bus System

3.4.1

Cabinet Installation

The Dual Bus System consists of two independent UPS configurations each consisting of one or more

UPS modules. Dual Bus Systems are high availability configurations suitable for loads with multiple

input terminals. For single input loads an optional Static Transfer Switch may be added and the stan-

dard Load Bus Synchroniser activated. Depending on the configuration, follow the appropriate instal-

lation instructions for each system.
Place the UPS modules side by side and interconnect as shown below.
The objective of the Dual-bus Synchronizer (DBS) is to keep the output of two independent UPS sys-

tems (or parallel systems) in synchronization. One system is designated as the master; the other is

designated as the slave. The operating modes covered comprise master and or slave operating

inverter or bypass mode.

Figure 33 Typical dual bus system configuration with static transfer switch and Load Bus Synch

3.4.2

External Protective Devices

Refer to the instructions supplied in 1.0 - Single Module UPS Installation.

3.4.3

Power Cables

The wiring of power cables is similar to that of single module system. The Bypass and the Main input

sources must be referenced to the same neutral potential and input earth leakage monitoring devices,

if installed, must be located upstream of the common neutral sinking point. Refer to the instructions

in 1.0 - Single Module UPS Installation

STS

Load

UPS1

Q1

CHARGER

RECTIFER

INVERTER

Q5

Q3

Q2

UPS1

Q1

CHARGER

RECTIFER

INVERTER

Q5

Q3

Q2

LBS

Input

Rectifier

Input

Rectifier

Bypass Supply

UPS1

Q1

CHARGER

RECTIFER

INVERTER

INTERMODULE

CONTROL CABLE

Q5

Q3

Q2

UPS1

Q1

CHARGER

RECTIFER

INVERTER

Q5

Q3

Q2

Input

Rectifier

Input

Rectifier

Bypass Supply

INTERMODULE

CONTROL CABLE