Single Module UPS Installation

12

1.8

Dry Contacts

The UPS provides input dry contacts and output dry contacts.

1.8.1

Input Dry Contacts

There are several input dry contacts at the X3 slot.

X3 Ancillary Control and Alarms

X3 IN DRY: Environmental, Battery Ground Fault and Generator Contacts
The UPS accepts external signalling from voltage-free (dry) contacts connected to finger-proof, push-

in terminal X3 IN DRY. Subject to prior software programming, the signalling is accepted by the UPS

when connection between the relevant terminal and the +12V terminal is altered. Cables connected to

X3 IN DRY must be segregated from power circuits (for screening purposes), double insulated and of a

typical 0.5 to 1mm

2

cross-section area for maximum runs between 25 and 50 meters (82-164 ft),

respectively.

Figure 3

Input dry contacts

Table 3

Input dry contacts at X3

Position

Name

Description

J4.1

ENV

3

Battery Room Alarm (NC)

J4.2

BtG

Battery Ground Fault Detection (NC)

J4.3

GEN

1,2

On Generator (NO)

J4.4

+12V

+12V Power

1 - Must be configured by configuration software before becoming active.
2 - When activated, the charger current can be limited, via software, to a percentage of the full charger current (0-100%).
3 - Activating this feature turns the battery charger off.

NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm

2

(16-20AWG) stranded for maximum runs between 25 and 50m (82-164 ft.) respectively.