Technical Specifications

116

Table 34

Efficiency, AC/AC

Input and output voltage 400VAC, battery charged, full rated linear load

Rated Power, kVA

Unit of

Measurement

30

40

60

80

100

120

140

160

200

Normal Mode
(dual conversion)

%

89

90

91

91

90.6

91.1

92.5

92.7

92.8

ECO Mode

%

94

94.8

94.3

95

95

95.6

95.5

95.7

95.7

Inverter Efficiency (DC/AC) (battery at nominal voltage 480VDC and full-rated linear load)

Battery Mode

%

93

93

94

94

94

94

94

94

94

Heat Losses & Air Exchange—Ventilation

Normal Mode

kW

3.0

3.6

4.7

6.3

7.9

9.5

10.8

11.8

14.5

ECO Mode

kW

1.5

1.6

2.0

2.6

3.5

4.3

7.0

7.6

9.9

No Load

kW

1.3

1.4

1.9

2.4

3.0

3.7

4.9

4.9

5.6

Forced air cooling

(front intake, top exhaust)

L/sec

333

333

458

458

500

500

671

671

721

M

3

/hr

1200

1650

1800

2415

2595

Table 35

Mechanical characteristics

Rated Power, kVA

Unit of

Measurement

30

40

60

80

100

120

140

160

200

Dimensions, H x W x D

mm (in)

1600 x 600 x 825

(63 x 23.6 x 32.5)

1800 x 700 x 825

(70.8 x 27.5 x 32.5)

1800 x 1000 x 825

(70.8 x 39.4 x 32.5)

Mass, without batteries

kg (lb)

312

(688)

341

(752)

401

(884)

445

(981)

720

(1587)

720

(1587)

960

(2116)

960

(2116)

1060

(2337)

Finish

Colour

Pantone 877 (Silver grey)

eqvl Becker Silver epoxy polyester powder 041-37-2

Protection Degree

IEC 60529

IP20

(finger-proof with front doors open or closed)

Values listed are the mass of the units with options added (ground fault sensor, bypass share inductors and redundant fans).

Table 36

Rectifier AC input (mains)

Rated power, kVA

Unit of

Measurement

30

40

60

80

100

120

140

160

200

Rated AC Input Voltage

1

VAC

380/400/415 V

(three-phase and sharing neutral with the bypass input)

Input voltage tolerance

2

VAC

305V to 477V 304V to 208V (output de-rated from 99% to 70%)

Frequency

1

Hz

50/60Hz (tolerance 40Hz to 72Hz)

Power Factor

full load

kW/kVA

0.99

0.99

0.99

0.99

0.99

0.99

0.99

0.99

0.99

half load

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

Input power

rated

3

kVA

27.2

35.9

53.3

71.0

88.8

107

122

139

174

maximum

4

32.9

43.0

64.6

85.2

107

128

159

182

228

Input current

rated

3

A

39

52

77

103

128

154

177

201

252

maximum

4

48

62

93

123

154

185

231

264

330

Harmonic Current Distort (with
linear or non-linear balanced
load and at input THVD

2%)

THID
% FL

3

3

3

3

3

3

3.5

3

3

Duration of progressive power
walk-in

sec

10 seconds to reach full rated current

(selectable 5 through 30 seconds in 5 second intervals)

1.

Rectifier operates at any of the rated supply voltages and frequencies without further adjustment.

2.

At 305V input mains, the UPS maintains the specified output voltage at rated load without discharging a previously charged battery.

3.

EN 50091-3: at rated load and input voltage 400V, battery charged

4.

EN 50091-3: at rated load and input voltage 400V, battery charging at maximum rated power.