beautypg.com

0 maintenance, 1 repair, 2 inspection and cleaning – Emerson Liebert FPC User Manual

Page 38: 1 inspection schedule, Aintenance, Repair, Inspection and cleaning, Inspection schedule, Warning

background image

Maintenance

34

5.0

M

AINTENANCE

5.1

Repair

Even the most reliable equipment may fail. Liebert Global Services is at your service to assure fast

repair of your unit and minimum downtime of your installation.

Standard electrical troubleshooting procedures should be used to isolate problems in the unit. If there

are questions, don’t hesitate to contact Liebert Global Services.
Repair or replacement of standard items, such as circuit breakers, fuses, transformers, capacitors and

indicator lights can either be handled by qualified electricians or referred to Liebert Global Services.
Repairs related to the monitoring system should be referred to Liebert Global Services. To contact

LGS for information or repair service in the United States, call 1-800-LIEBERT.

5.2

Inspection and Cleaning

Air circulation through the cabinet may cause dust to accumulate on internal components. Cleaning

should be done as necessary during electrical inspections.
Annual general system inspections, cleaning, and operation checks are recommended to ensure sys-

tem performance and long service life.

5.2.1 Inspection Schedule

• It is difficult to establish a schedule for periodic cleanings because conditions vary from site to

site. Inspections after the first 24 hours, 30 days and 6 months of operation should help determine

a pattern for the inspection schedule.

• Electrical connections and component mountings should be inspected after the first 24 hours,

30 days, and 6 months of operation. Inspections should be conducted annually thereafter.

• Ventilation openings and grilles should be inspected and cleaned every 6 months to one year.
• A complete inspection and operational checkout should be performed annually. This is best done

by performing the inspection and start-up procedure as detailed in 3.0 - Inspection and Star-

tup Checklist.

• LGS offers a complete range of preventive maintenance services. These include thorough equip-

ment performance checks and calibration of electronics. Contact Liebert Global Services in the

United States by calling 1-800-LIEBERT for details.

!

WARNING

Only qualified service personnel should perform maintenance on the Liebert FPC system.

!

WARNING

Only qualified service personnel should perform maintenance on the Liebert FPC system. All

voltage sources to the unit must be disconnected before inspecting or cleaning within the

cabinet.