20

1.3.6 Control Wiring Connections

NEC Article 645 requires that emergency power off (EPO) switches be located at the principal room

exits. All standard Liebert power conditioning systems have provisions for external shutdown control

from Remote Emergency Power Off (REPO) stations. Figure 14 is a simplified diagram of the shut-

down circuitry of the Liebert FPC.

Low-Voltage Control Circuit

Control wiring connections must comply with the NEC and all other applicable codes.

As shown in Figure 14, the control circuit operates on 24VDC. The shutdown device (represented by

the REPO switch) activates a low-current, 24VDC relay that in turn operates the shunt-trip mecha-

nism. The shunt-trip solenoid opens the Main Input Breaker, which de-energizes the power center.

Multiple-Unit Shutdown

When more than one power center is installed by the user, a typical requirement is that actuation of a

single device (REPO for example) must shut down all power centers. The low-voltage control circuits

of all standard Liebert FPC systems are designed to meet this requirement.

External Control Wiring Connections

External control wiring connections for remote shutdown, alarm, and/or monitoring are made to the

low-voltage junction box (if used) or to the low-voltage control terminal strip located inside the unit.
Control wiring connections vary with the type of monitoring system furnished with the unit. Two typ-

ical control wiring configurations are shown in Figures 15 and 16.

Figure 14 Simplified shutdown circuit

!

WARNING

Verify that all incoming high-voltage (power) and low-voltage (control) circuits are

de-energized and locked out before installing cables or making connections, whether in the

junction box or in the unit.

+

-

K5

K6

6

2

3

4

1

N.O. REPO

Overtemp

Switch

N.C. REPO

R1

B

9

6

3

7

4

1

A

Main
Input
Breaker
Shunt
Trip

K5

K6

+24VDC

Unit EPO

Remote

Shutdown

Devices

Building

Interface

Relay

24VDC

Source

Liebert FPC