Installation Instructions

14

1.3.2 Junction Box Installation

Main input (power) and low-voltage (control) junction boxes are available for the Liebert FPC to sim-

plify customer connections.
The junction boxes, if used, can either be shipped with the system or can be advance-shipped for

installation during the roughing-in stage of new construction.
Liebert supplies flexible, 10-foot-long (3m) conduit with cables for connecting the junction boxes to the

unit. The junction boxes should be installed a maximum of 8 ft. (2.4m) from the feeder entrance of the

unit.
Liebert recommends centering the junction boxes under a floor tile that is easily removed.
Junction box connections must be installed in compliance with the NEC and all other applicable

codes.

Typical junction box connections are shown in Figure 16 and described in 1.3 - Power and Control

Wiring.

Dimensions are given on the drawings furnished with the unit. Typical dimensions of the junction

boxes are as follows:

!

WARNING

Verify that incoming line voltage (power) and low-voltage (control) circuits are de-energized

and locked out before installing cables or making any connections in the junction box.

Table 6

Main input junction box electrical connections (4 wire)

Junction Box Size

Inches (mm)

Electrical Connections

27 x 14 x 6

(686 x 356 x 152)

400A 3 pole power block with 1/2 -13 studs on 1-3/4" (44mm) centers

750A ground busbar with two sets of 3/8 - 16 studs on 1.75” centers

35 x 22 x 6

(889 x 559 x 152)

750A phase busbars with 1/2 -13 studs on 1-3/4" (44mm) centers

750A ground busbar with two sets of 3/8 -16 studs on 1-3/4" (44mm) centers

Table 7

Main input junction box without transformer electrical connections (5 wire)

Junction Box Size

Inches (mm)

Electrical Connections

27 x 14 x 6

(686 x 356 x 152)

400A 3 pole power block with 1/2 -13 studs on 1-3/4" (44mm) centers

750A neutral busbar with two sets of 1/2 -13 studs on 1-3/4" (44mm) centers

750A ground busbar with two sets of 3/8–16 studs on 1-3/4" (44mm) centers

35 x 22 x 6

(889 x 559 x 152)

750A phase busbars with 1/2 -13 studs on 1.75” centers

1500A neutral busbar with two sets of 1/2 -13 studs on 1-3/4" (44mm) centers

750A ground busbar with two sets of 3/8 - 16 studs on 1-3/4" (44mm) centers

Table 8

Low-voltage (control) junction box dimensions, typical

Width, inches (mm)

8 (203)

Length, inches (mm)

10 (254)

Height, inches (mm)

4 (102)

Table 9

Main input (power) junction box dimensions, typical

Unit kVa

Input Voltage

208-240V

380-415V

480-600V

15-100 kVA, L x W x H, inches (mm)

27 x 14 x 6 (686 x 356 x (152)

125-150 kVA, L x W x H, inches (mm)

35 x 22 x 6

(889 x 559 x 152)

27 x 14 x 6 (686 x 356 x (152)

200 kVA, L x W x H, inches (mm)

N/A

27 x 14 x 6 (686 x 356 x (152)

225 kVA, L x W x H, inches (mm)

N/A

35 x 22 x 6

(889 x 559 x 152)

27 x 14 x 6

(686 x 356 x (152)

300 kVA, L x W x H, inches (mm)

N/A

35 x 22 x 6 (889 x 559 x 152)