0 operating instructions, 1 startup procedures, 2 normal system shutdown – Emerson Liebert FPC User Manual
Page 33: 3 normal system turn on, 4 manual restart, Perating, Nstructions, Startup procedures, Normal system shutdown, Normal system turn on
Operating Instructions
29
4.0
O
PERATING
I
NSTRUCTIONS
4.1
Startup Procedures
Before the unit is placed into service after initial installation, after equipment relocation, or after
equipment has been de-energized for an extended period of time, perform equipment inspection and
start-up procedures as detailed in 2.0 - Equipment Inspection and Startup and 3.0 - Inspection
and Startup Checklist.
After initial system startup, the following guidelines can be used for standard equipment operation.
These guidelines should be reviewed for any special equipment modifications, special site consider-
ations or company policies that may require changes to the standard equipment operation.
4.1.1 Emergency Shutdown—If Emergency Power Off switch is supplied
To perform an immediate system shutdown during emergency conditions, lift the clear protective
cover and push the Emergency Power Off (EPO) switch on the FPC’s monitoring panel.
If the site is equipped with a Remote Emergency Power Off (REPO) switch to perform an immediate
room shutdown, actuate one of the REPO switches. NEC Article 645 requires a REPO switch at the
principal exit doors.
4.1.2 Normal System Shutdown
To perform a normal system shutdown, perform an orderly load equipment shutdown according to the
load equipment manufacturer’s recommended shutdown sequence. The load equipment can be turned
OFF at each piece of load equipment or at the FPC’s output distribution (circuit breaker) panels
located behind the FPC’s front door. Turn OFF all unit output breakers, then turn OFF the unit’s
main input circuit breaker. To remove all power from the FPC, turn OFF the building power to the
FPC’s input breaker or junction box.
4.1.3 Normal System Turn ON
Make certain all of the FPC’s circuit breakers are in the OFF position. All unit circuit breakers are
located behind the front doors. Turn ON building power to the FPC. Turn ON the FPC’s main input
circuit breaker. If the circuit breaker has been tripped OFF (instead of being turned OFF), the circuit
breaker handle must be moved to the OFF position before being turned ON. If the FPC has a voltage
monitoring panel, verify proper output voltages before turning ON output circuit breakers. Turn ON
the panelboard main breakers. Individually turn ON each output circuit breaker following the load
equipment manufacturer’s startup sequence.
4.1.4 Manual Restart
If the FPC’s manual restart feature has been selected, the unit’s main input circuit breaker will be
tripped upon a power failure, preventing repetitive application of unstable voltage and allowing for an
orderly system restart. If the main input circuit breaker is tripped upon a power failure, wait until
power is restored, then follow the instructions in 4.1.3 - Normal System Turn ON.
NOTE
Depending on the particular control circuit wiring, operation of the unit EPO switch may cause
other equipment to also shutdown.