Operating Instructions

32

To Set Unit Clock - To set the clock from the unit front panel, simultaneously press the Scan and

Hold membrane switches while the time and date screen is displayed on the LCD. A cursor should

appear on the selected time and date field. Use the Scan switch to increment the highlighted field and

the Hold switch to decrement the highlighted field. Use the Silence push button to select the next

time and date field. The time can be displayed in AM/PM or 24-hour format. Simultaneously press the

Scan and Hold switches to exit the clock set screen.
RS-232 ASCII Communications Port - Units with power monitoring are equipped with an isolated

RS-232 ASCII Communications Port, which allows access to unit monitored parameters and alarm

information. The RS-232 port connections are located on the low voltage control terminal strip inside

the unit. See typical control wiring in Figure 16.
The ASCII interface default parameters are shown in Table 15.

The ASCII port uses a Query-Response Format.
Table 17 shows the list of available customer commands. Only one command is serviced at a time.

Valid commands are terminated with a carriage return [0Dh]. Commands are accepted in upper or

lower case. Responses are in upper case, terminated with a line feed [0Ah] and carriage return [0Dh].

Table 15

ASCII interface default parameters

Parameter

Default

Interface

RS-232 using EIA voltage levels

Baud rate

9600

Parity None
Data bits

8

Stop bits

1

Terminator
Hand shaking

Not supported

Structure Half-duplex
Echo OFF
Change to receive after transmit

1.28 msec

Minimum delay to transmit after receive

120 µsec

Maximum response time turn around

300 msec

Maximum response completion time

500 msec

Minimum delay between commands

500 msec

Maximum intercharacter delay

12.5 msec

Table 16

RS-232 ASCII port customer commands

Command

Description

Typical Response

Time?

Date?

Unit: Time

Unit: Date

03:40:37A

05-15-97

UID?

kVA?

V?

Unit ID

Nominal kVA

Nominal L-L Voltage

Unit_No._PDU_21B____

0150

0208

SS1?

System Information

(20-character fields

with comma separators)

UNIT_MODEL_NUMBER___SERIAL NUMBER_______

SITE_ID_NUMBER______TAG_NUMBER__________

SA?

Number of Active Alarms

(20-character alarms

with time stamp)

02, OUTPUT_OVERVOLTAGE__05-15-97,01:25:30A

OUTPUT_OVERCURRENT__05-15-97,01:27:46A

UPMD?

Monitored Parameters

(32 comma-separated

data fields—see

Table 17 for descriptions

of field positions)

0484,0485,0483,0210,0212,0211,0121,0122,0121,0068,

0085,0120,0131,0018,0030,0092,0033,0600,0038,0041,

0043,0549,0632,0599,0000,1528,0018,0019,0020,0045,

0047,0049,0044