Figures 15, Low voltage terminal strip – Emerson Liebert FPC User Manual

Page 25

background image

Installation Instructions

21

Figure 15 Typical control wiring for units without monitoring

21
20
19
18
17
16
15
14
13
12
11
10

9
8
7
6
5
4
3
2
1

F

a

ct

or

y-

S

upp

lied

W

ir

in

g

R

24VDC W204

Overtemp Alarm N.O. W208
Overtemp Alarm N.C. W207

N.O. REPO W205

Alarm Com. W206

REPO Com. W203

N.C. REPO W202

24VDC W201

Building
Interface
Relay

Overtemp
Alarm Output

S

N.O. REPO

N.C. REPO

Remove jumper
when Normally
Closed (N.C.)
REPO is used

GRN

BLK
WHT

Low Voltage
Terminal Strip

7

A

B

9

6

3

1

4

NOTES

1. All switching devices are to be suitable for switching low current 24VDC. Minimum

recommended wire size is 18AWG stranded copper with 300V insulation.
All wiring and devices are field supplied except where noted. See installation manual for

detailed installation procedures.

2. Low voltages terminal strip may be located in unit or low voltage control junction box.
3. The total load on the 24VDC supply (both N.O. and N.C. REPO circuits) must be limited to

1A.

4. Multiple normally open (N.O.) REPO switches may be paralleled.

Multiple normally closed (N.C.) REPO switches may be connected in series. all lamps (if used)

are connected in parallel.

5. The summary alarm contacts are rated for 0 to 30VAC or VDC, 0.5A, 10W maximum.