Installation, Figure 5, incorrect dc wiring – Magnum Energy Series Stacking Cable Kit (ME-SSI) User Manual
Page 11
![background image](https://www.manualsdir.com/files/821316/content/doc011.png)
©
2010 Magnum Energy, Inc.
Installation
6
Figure 5, Incorrect DC Wiring
6 volt
battery
6 volt
battery
6 volt
battery
6 volt
battery
6 volt
battery
6 volt
battery
6 volt
battery
6 volt
battery
This battery bank uses two battery strings . They must
be connected together in parallel to provide a single
battery bank to the inverters .
The battery bank
cables are going to
one inverter, this is
NOT RECOMMENDED
DC disconnect and
overcurrent protection
DC Positive and
Negative
Interconnects
(from ME-SSI kit)
MS4024
L1
inverter
MS4024
L2
inverter
INCORRECT WAY TO CONNECT THE BATTERY
BANK TO THE SERIES STACKED INVERTERS .
**DO NOT WIRE THIS WAY**
Stacker cable
(from ME-SSI kit)
Incorrect DC wiring – As shown in Figure 5, do not attempt
to connect the positive and negative to one inverter and then
jumper the negative and positive to the second inverter. This will
not distribute the current into and out of the battery bank evenly
and may not allow the second inverter to receive suffi cient current
if powering a heavy load. If you have a single battery cable pair,
use Figure 3 to guide you in wiring your DC battery cables to the
stacked pair of inverters.
•