Installation – Magnum Energy Series Stacking Cable Kit (ME-SSI) User Manual
Page 10
©
2010 Magnum Energy, Inc.
6 volt
battery
6 volt
battery
6 volt
battery
6 volt
battery
6 volt
battery
6 volt
battery
6 volt
battery
6 volt
battery
This battery bank uses two battery strings . They must
be connected together in parallel to provide a single
battery bank to the inverters .
DC Negative
Interconnect
(from ME-SSI kit)
DC disconnects and
overcurrent protection
MS4024
L2
inverter
MS4024
L1
inverter
This diagram is for a 24 VDC
battery system. Ensure your
battery bank is wired correctly .
Stacker cable
(from ME-SSI kit)
Figure 4, DC Wiring Using Two Battery Cable Pairs
DC Wiring Using Two Battery Cable Pairs – Each inverter
has its own battery cable pair (positive and negative for each
inverter) connected to the battery bank. There are two DC discon-
nect/overcurrent devices, one for each positive battery cable. Use
only the DC negative interconnect cables from the ME-SSI kit be-
tween the two inverters in this confi guration. The positive intercon-
nect cable is not used in this installation as it may not meet electri-
cal code requirements, and would cause performance issues if only
one DC disconnect/overcurrent device inadvertently opens.
•
Installation
5