3.2 External
Settings
The generator run time, temperature, and voltage settings come pre-set
directly from the factory. For the majority of customers, the factory default
settings as shown in Table 3-2 are appropriate. If you need to make changes
to the factory settings, you can do so by rotating the knobs on the front panel
of the AGS controller either clockwise or counterclockwise (see Figure 3-3).
QUIET TIME
PM/AM
setting
CLOCK
AM/PM
setting
START
VOLTS DC
setting
START
TEMP
°F
setting
RUN TIME
HOURS
setting
RUN TIME HOURS: This setting determines the length of time the generator
runs once started. The generator starts because the battery voltage has
fallen to the START VOLTS DC setting for at least two continuous minutes;
or, the temperature around the remote switch has risen to the START TEMP
°F setting. The run time can be set from 1-5 hours. To change this setting,
slowly rotate the knob marked RUN TIME HOURS clockwise to increase
generator run time or counterclockwise to decrease the generator run time.
Adjustable Settings
Factory Default Values
RUN TIME HOURS
2 (Hours)
START TEMP °F
OFF (disabled)
START VOLTS DC
11 (Volts DC)
CLOCK AM/PM
8A (8 AM)
QUIET TIME PM/AM
OFF (disabled)
INPUT DC VOLTAGE
12 Volts (bottom two pins)
GEN TYPE
QD Mode (all 4 switches off)
EXTERNA
L
SETTI
NGS
IN
TERNA
L
SETTINGS
Table 3-2, ME-AGS-S Default Settings
Figure 3-3, External Settings
Setup