Installation, Figure 2-10, three-wire momentary type generators, Inside generator – Magnum Energy AGS Stand Alone (ME-AGS-S) User Manual
Page 18: Relay timing for gen type: 5-wire mode

15
© 2013 Magnum Energy, Inc.
Monitored
battery bank
(12V/24V/48V)
12/24/48V
GEN TYPE
(5-wire mode)
≤5
amp
fuse
≤5
amp
fuse
≤5
amp
fuse
INPUT DC
VOLTAGE JUMPER
- set to monitored
battery bank voltage
(on 24V setting)
INSIDE
INSIDE
ON
4
3
2
1
Inside Generator
Gen
Battery
Gen
Hour Meter
0 1 2 3
PREHEAT
START
STOP
≤5
amp
fuse
GEN AND POWER I/O
Relay 1
(Terminals 5 & 6)
Relay 2
(Terminals 6 & 7)
Relay timing for GEN TYPE: 5-wire Mode
STOP
Time
START
Time
Time between start attempts
10 sec.
10 sec.
4 sec.
Timing Information
Total start attempts
2 minutes
PREHEAT
Time
25 sec.
Relay 3
(Terminals 1 & 8)
Start
Delay
Delay
RUN TIME
HOURS
PREHEAT
START
STOP
STOP
4
Preheat delay time
Start Delay Time
14 sec.
Figure 2-10, Three-wire Momentary Type Generators
Installation