Installation, Figure 2-9, two-wire start type generators, Inside generator ground – Magnum Energy AGS Stand Alone (ME-AGS-S) User Manual
Page 17: Relay timing for gen type: 2-wire maintain mode

© 2013 Magnum Energy, Inc.
14
Installation
Gen
Battery
≤5
amp
fuse
Monitored
battery bank
(12V/24V/48V)
≤5
amp
fuse
Run / Off
Switch
Inside Generator
Ground
≤5
amp
fuse
12/24/48V
ON
4
3
2
1
GEN TYPE
(2-Wire
Maintain
Mode)
INPUT DC
VOLTAGE JUMPER
- set to monitored
battery bank voltage
(on 24V setting)
Gen
Hour Meter
0 1 2 3
GEN AND POWER I/O
R2
Relay 1
(Terminals 5 & 6)
Delay
Relay 2
(Terminals 6 & 7)
RUN TIME HOURS
RUN
OFF
Relay timing for GEN TYPE: 2-Wire Maintain Mode
R2 (Relay 2) Time
Delay time
Time between start attempts
10 sec.
4 sec.
2 min.
Timing Information
Total start attempts
4
Relay 3
(Terminals 1 & 8)
OFF
INSIDE
INSIDE
Figure 2-9, Two-wire Start Type Generators