9 shutdown/disassembly, 9shutdown/disassembly, Danger – KACO Powador-gridsave User Manual
Page 22

Page 22
Battery unit extension - Panasonic / Sanyo for Powador-gridsave
Shutdown/Disassembly
9
Shutdown/Disassembly
DANGER
Lethal voltages are still present in the terminals and cables even
after switching off and disconnection of the battery system.
Severe injuries or death may occur if the cables and terminals in the
device are touched.
›
Complete de-energisation only occurs if the bulk power supply is
switched off upstream of the battery system.
Remove battery (batteries) from the Battery Management System (BMS).
↻ Battery system disconnected from the DC and AC supply.
1. Remove plexiglass cover
2. Remove DC breakers from the battery(ies).
3. Disconnect communication between the battery and the Battery Manage-
ment System (BMS). (Including terminator)
4. Remove covers on the Battery Management System (BMS) contacts and
the battery poles.
5. Remove the busbar on the (-) minus pole.
6. Remove the busbar on the (+) plus pole.
7. Fit covers on the Battery Management System (BMS) contacts and the
battery poles.
8. Remove fixing bracket from the battery(ies).
9. Place battery(ies) in the original packaging.
10. Fit Plexiglass cover in the battery system.
»
Disassembly complete.
NOTE
Observe the remaining instructions in the operating manual for the
Powador-gridsave battery system (chapter 11).