blueplanet Operating and Installation Instructions 1502x - 2502x

Installation and Start-Up

NOTE

Be sure to use cables with a suffi ciently large cross-section
to avoid excessive line impedance between the building’s
distribution box and the respective blueplanet unit.
When the line impedance is high, i.e. long AC-side leads,
the voltage at the line terminals of the inverter will increase
as power is being fed in to the grid. The inverter measures
this voltage. If the voltage at the grid terminals exceeds the
line overvoltage limit, the inverter will switch off due to line
overvoltage. This condition must be taken into consideration
when wiring the AC and dimensioning the AC lead.

!

CAUTION

Check that the leads are properly connected.

ACTION

Once again, ensure that all connected leads are fi rmly
connected.

PV generator connection

The PV generator leads are connected to the bottom plate of
the inverter.