Installation – Ion Science Hydrosteel 7000 User Manual
Page 13
Hydrosteel 7000 MANUAL
Ion Science Ltd
Page 13 of 43
Unrivalled Detection. www.ionscience.com
Electrical connections (IS) with safety barriers
Yellow Connector
Thermocouple
junction box
Thermocouple
2
3
E
SCREEN
+V RD
0V BK
Red Connector
SA
FE
A
RE
A
1
SCREEN
+V RD
0V BK
1
E
3
2
SCREEN
0V BK
+V RD
2
E
3
1
Blue Connector
Hydrosteel 7000
0V
+V
BK
RD
4-20mA 1
0V
+V
0V
RD
BK
Power
+V
BK
RD
4-20mA 2
Control equipment
Installation
Ion Science Ltd suggest using the following or similar safety barrier or IS isolator for IS approved
applications. The system must be designed by a suitably trained engineer and approved by the local safety
authority.
Power Supply:
Suggested barriers for INLET power supply
Manufacture
Manufactures pt. no.
Type
Cable length estimate
m
Pepperl & Fuchs
KFD2-VD-Ex1.1835
Galvanic Isolator
560
Stahl
9175-10-16-11
Galvanic Isolator
335
MTL Ltd
MTL4023
Galvanic Isolator
365
MTL Ltd
MTL7728P
Zener barrier
288
Turck
MK72S06-EX
Galvanic Isolator
686
* Note
All cable lengths are estimated for Zone 1 IIC installation of the equipment
Using 1 mm
2
C.S.A. conductors S.T.P. cables with capacitance of 250 pF/m, L/R ratio of 25 uH/
conductor resistance at 20
C of 18.4
/Km
Calculation assumes that cables are at 80
C (maximum operating temperature).
Signal Output
Suggested barriers for 4-20mA OUTLET
Manufacture
Manufactures pt. no.
Type
Pepperl+Fuchs
Z728
Zener barrier
Pepperl+Fuchs
KFD2STC4-Ex1
Galvanic isolator
MTL
MTL7787 (dual channel)
Zener barrier
MTL
MTL5044 (dual channel)
Galvanic isolator
Stahl
9001/51-280-110-141
Zener barrier
Stahl
9160/13-11-11S
Galvanic isolator
WARNING! Intrinsically safe (IS) applications
HY7K fuses may not be replaced in the field.
If a fuse is blown the Hydrosteel 7000 will require inspection by Ion Science Ltd or and Ion Science Approved
Service Centre before it is used in an IS application.