4.1 MECHATROLINK-II Communications Settings

4-3

4

Ope

rat

ion

4.1 MECHATROLINK-II Communications Settings

This section describes the switch settings necessary for MECHATROLINK-II communications.

4.1.1 Setting Switches S2 and S3

The S3 DIP switch is used to make the settings for MECHATROLINK-II communications.

The station address is set using the rotary switch (S2) and the DIP switch (S3).

(1) Settings for the S3 DIP Switch

The following table shows the settings of the DIP switch (S3).

4

3

5

2

6

1

7

C

8

0

F

9

E

A

D

B

ON

OFF

1

2

3

4

S3

Seven-segment
LED display

POWER LED

S2

M-II

SW2

Function

Setting

Description

Factory setting

Pin 1 Sets the baud rate.

OFF

4 Mbps (MECHATROLINK-I)

ON

ON

10 Mbps (MECHATROLINK-II)

Pin 2 Sets the number of trans-

mission bytes.

OFF

17 bytes

ON

ON

32 bytes

Pin 3 Sets the station address.

OFF

Station address = 40H + S2

OFF

ON

Station address = 50H + S2

Pin 4 Reserved. (Do not change.)

OFF

OFF

• When connecting to a MECHATROLINK-I network, turn OFF pins 1 and 2.
• When using a MECHATROLINK-I network (Baud rate: 4 Mbps), the settings for the num-

ber of transmission bytes is disabled and the number of transmission bytes is always 17.