Yaskawa Sigma-5 User Manual: Design and Maintenance - Linear Motors User Manual
Page 278

8.2 Warning Displays
8-27
8
T
roubleshooting
A.920
Regenerative
Overload:
Warning before
the alarm A.320
occurs
The power supply volt-
age exceeds the speci-
fied range.
Measure the power supply voltage.
Set the power supply voltage within
the specified range.
The external regenera-
tive resistance, SERVO-
PACK capacity, or
regenerative resistor
capacity is insufficient
or a continuous regener-
ative state occurs.
Check the operating conditions or
capacity using the capacity selection
software SigmaJunmaSize+, etc.
Change the regenerative resistance,
regenerative resistor capacity, or SER-
VOPACK capacity. Reconsider the
operating conditions using the capac-
ity selection software SigmaJunma-
Size+, etc.
Regenerative power
continuously flowed
back because negative
load was continuously
applied.
Check the load on the linear servo-
motor during operation.
Reconsider the system including the
servo, machine, and operation condi-
tions.
A921
Dynamic Brake
Overload:
Warning before
the alarm A.731
occurs
The linear servomotor is
driven by an external
force.
Check the operating conditions.
Do not drive the linear servomotor
with external force.
The moving energy at a
DB stop exceeds the DB
resistance capacity.
Check the operating frequency of the
DB with power consumed by DB
resistance (Un00B).
• Reduce the linear servomotor refer-
ence speed.
• Reduce the mass.
• Reduce the number of times of the
DB stop operation.
A SERVOPACK fault
occurred.
–
The SERVOPACK may be faulty.
Replace the SERVOPACK.
A.94A
Command
Option Module
IF Data Setting
Warning 1
An incorrect parameter
number was sent to the
SERVOPACK from the
host controller or com-
mand option module.
–
Specify the correct parameter number.
A.94B
Command
Option Module
IF Data Setting
Warning 2
Out-of-range data was
sent to the SERVO-
PACK from the host
controller or command
option module.
–
Specify the value of the parameter
within the allowable range.
A.94C
Command
Option Module
IF Data Setting
Warning 3
Incorrect parameter data
was sent to the SERVO-
PACK from the host
controller or command
option module.
–
Specify the value of the parameter
within the allowable range.
A.94D
Command
Option Module
IF Data Setting
Warning 4
The incorrect parame-
ter size was sent to the
SERVOPACK from the
host controller or com-
mand option module.
–
Specify the correct parameter size.
A.94E
Command
Option Module
IF Data Setting
Warning 5
Incorrect latch mode
settings were sent to the
SERVOPACK from the
host controller or com-
mand option module.
–
Set a proper value for the latch mode.
A.95A
Command
Option Module
IF Command
Warning 1
The host controller or
command option mod-
ule sent a operating
command when the
operation execution
conditions in the SER-
VOPACK had not been
satisfied.
–
Send a command after the operation
conditions are satisfied.
Warning
Display
Warning Name
Situation at Warning
Occurrence
Cause
Corrective Actions