8.2 Warning Displays
8-27
8
T
roubleshooting
A.920
Regenerative
Overload:
Warning before 
the alarm A.320 
occurs
The power supply volt-
age exceeds the speci-
fied range.
Measure the power supply voltage.
Set the power supply voltage within 
the specified range.
The external regenera-
tive resistance, SERVO-
PACK capacity, or 
regenerative resistor 
capacity is insufficient 
or a continuous regener-
ative state occurs.
Check the operating conditions or 
capacity using the capacity selection 
software SigmaJunmaSize+, etc.
Change the regenerative resistance, 
regenerative resistor capacity, or SER-
VOPACK capacity. Reconsider the 
operating conditions using the capac-
ity selection software SigmaJunma-
Size+, etc.
Regenerative power 
continuously flowed 
back because negative 
load was continuously 
applied. 
Check the load on the linear servo-
motor during operation.
Reconsider the system including the 
servo, machine, and operation condi-
tions.
A921
Dynamic Brake
Overload: 
Warning before 
the alarm A.731 
occurs
The linear servomotor is 
driven by an external 
force.
Check the operating conditions.
Do not drive the linear servomotor 
with external force.
The moving energy at a 
DB stop exceeds the DB 
resistance capacity.
Check the operating frequency of the 
DB with power consumed by DB 
resistance (Un00B).
• Reduce the linear servomotor refer-
ence speed.
• Reduce the mass.
• Reduce the number of times of the 
DB stop operation.
A SERVOPACK fault 
occurred.
–
The SERVOPACK may be faulty. 
Replace the SERVOPACK.
A.94A
Command
Option Module
IF Data Setting
Warning 1
An incorrect parameter 
number was sent to the 
SERVOPACK from the 
host controller or com-
mand option module.
–
Specify the correct parameter number.
A.94B
Command
Option Module
IF Data Setting
Warning 2
Out-of-range data was 
sent to the SERVO-
PACK from the host 
controller or command 
option module.
–
Specify the value of the parameter
within the allowable range.
A.94C
Command
Option Module
IF Data Setting
Warning 3
Incorrect parameter data 
was sent to the SERVO-
PACK from the host 
controller or command 
option module.
–
Specify the value of the parameter 
within the allowable range.
A.94D
Command
Option Module
IF Data Setting
Warning 4
The incorrect parame-
ter size was sent to the 
SERVOPACK from the 
host controller or com-
mand option module.
–
Specify the correct parameter size.
A.94E
Command
Option Module
IF Data Setting
Warning 5
Incorrect latch mode 
settings were sent to the 
SERVOPACK from the 
host controller or com-
mand option module.
–
Set a proper value for the latch mode.
A.95A
Command
Option Module
IF Command
Warning 1
The host controller or 
command option mod-
ule sent a operating 
command when the 
operation execution 
conditions in the SER-
VOPACK had not been 
satisfied.
–
Send a command after the operation 
conditions are satisfied.
Warning
Display
Warning Name
Situation at Warning
Occurrence
Cause
Corrective Actions