Yaskawa Sigma-5 User Manual: Design and Maintenance - Linear Motors User Manual
Page 263

8 Troubleshooting
8.1.2 Troubleshooting of Alarms
8-12
A.550:
Maximum Speed 
Setting Error
The Pn385 setting is greater than 
the maximum speed.
Check the value of Pn385 and 
Un010 (maximum allowable motor 
speed or maximum allowable 
encoder output resolution).
Set Pn385 to a value equal to or 
lower than the motor maximum 
speed.
A.710:
A.720:
Overload 
A.710: High Load
A.720: Low Load
Incorrect wiring or contact fault
of linear servomotor and linear 
scale.
Check the wiring.
Confirm that the linear servomotor 
and linear scale are correctly wired.
Operation beyond the overload 
protection characteristics.
Check the linear servomotor over-
load characteristics and executed 
run command.
Reconsider the load conditions and 
operation conditions. Or, increase 
the linear servomotor capacity.
Excessive load was applied dur-
ing operation because the linear 
servomotor was not driven due to 
mechanical problems.
Check the executed run command 
and linear servomotor speed.
Remove the mechanical problems.
The setting of the linear scale
pitch (Pn282) is incorrect.
Check the setting of Pn282.
Correct the setting of Pn282.
The setting of the motor phase 
selection (Pn080.1) is incorrect.
Check the setting of Pn080.1.
Correct the setting of Pn080.1.
A SERVOPACK fault occurred.
−
The SERVOPACK may be faulty. 
Replace the SERVOPACK.
A.730:
A.731:
Dynamic Brake 
Overload
(An excessive power 
consumption of dynamic 
brake was detected.)
The linear servomotor moves 
because of external force.
Check the operation status.
Take measures to ensure the linear 
servomotor will not move because 
of external force.
The moving energy at a DB stop 
exceeds the DB resistance capac-
ity.
Check the DB resistor power con-
sumption (Un00B) to see how many 
times the DB has been used.
• Reduce the linear servomotor ref-
erence speed.
• Reduce the mass ratio.
• Reduce the number of times of 
the DB stop operation.
A SERVOPACK fault occurred.
−
The SERVOPACK may be faulty. 
Replace the SERVOPACK.
A.740:
Overload of Surge 
Current Limit Resistor
(The main circuit power 
is turned ON/OFF too 
frequently.)
The inrush current limit resistor 
operation frequency at the main 
circuit power supply ON/OFF 
operation exceeds the allowable 
range.
−
Reduce the frequency of turning the 
main circuit power supply ON/OFF.
A SERVOPACK fault occurred.
−
The SERVOPACK may be faulty. 
Replace the SERVOPACK.
A.7A0:
Heat Sink Overheated
(Detected when the heat 
sink temperature 
exceeds 100
°C.)
The surrounding air temperature 
is too high.
Check the surrounding air tempera-
ture using a thermostat.
Decrease the surrounding air tem-
perature by improving the SERVO-
PACK installation conditions.
The overload alarm has been 
reset by turning OFF the power 
too many times.
Check the alarm history display 
(Fn000) to see if the overload alarm 
was reported.
Change the method for resetting the 
alarm.
Excessive load or operation 
beyond the regenerative energy 
processing capacity.
Check the accumulated load ratio 
(Un009) to see the load during oper-
ation, and the regenerative load 
ratio (Un00A) to see the regenera-
tive energy processing capacity.
Reconsider the load and operation 
conditions.
Incorrect SERVOPACK installa-
tion orientation or/and insuffi-
cient space around the 
SERVOPACK.
Check the SERVOPACK installa-
tion conditions.
Install the SERVOPACK correctly 
as specified.
A SERVOPACK fault occurred.
−
The SERVOPACK may be faulty. 
Replace the SERVOPACK.
A.7AB:
Built-in Fan in 
SERVOPACK
Stopped
The fan inside the SERVOPACK 
stopped.
Check for foreign matter or debris 
inside the SERVOPACK.
Remove foreign matter or debris 
from the SERVOPACK. If the 
alarm still occurs, the SERVO-
PACK may be faulty. Replace the 
SERVOPACK.
Alarm:
Alarm Name
Cause
Investigative Actions
Corrective Actions
