8.1 Troubleshooting
8-15
8
T
roubleshooting
A.C20:
Phase Detection Error
The linear scale signal is weak.
Check the voltage of the linear scale 
signal.
Fine-adjust the installation status of 
the linear scale head, or replace the 
linear scale.
The count-up direction of the lin-
ear scale does not match the for-
ward direction of the motor 
moving coil.
Check the setting of Pn080.1 
(Motor Phase Selection).
Check the installation directions for 
the linear scale and motor moving 
coil.
Change the setting of Pn080.1 
(Motor Phase Selection).
Correctly reinstall the linear scale 
and motor moving coil.
The hall sensor signal is affected 
by noise.
−
Correct the FG wiring and take 
measures against noise for the hall 
sensor wiring. 
A.C21:
Hall Sensor Error
The hall sensor is protruding 
from the motor magnetic way. 
Check the hall sensor.
Correctly reinstall the motor mov-
ing coil or motor magnetic way.
The setting of the linear scale 
pitch (Pn282) is incorrect.
Check the setting of the linear scale 
pitch (Pn282).
Correct the value of Pn282.
The hall sensor wiring is incor-
rect.
Check the hall sensor wiring.
Correct the hall sensor wiring.
A hall sensor fault occurred.
−
Replace the hall sensor.
A.C22:
Phase Information 
Disagreement
The SERVOPACK phase data 
does not match that of the linear 
scale.
−
Execute polarity detection (Fn080).
Alarm:
Alarm Name
Cause
Investigative Actions
Corrective Actions