Application Overview 2-7
VFD Object Configuration Property Summary
Table 2.4 - VFD Object Configuration Property Summary
Property Name
Variable Type
Default
Parameter
Description
nciNmlSpeed
SNVT_rpm
1800 rpm
n/a
Configures nominal motor speed in rpm
nciNmlFreq SNVT_freq_hz
60Hz n/a
Configures nominal motor frequency in hertz All speed related data in percent are referenced
to this value
nciMinSpeed SNVT_lev_percent 0%
d2-02 Configures the minimum motor speed as a percentage of nciNmlFreq Sets the drive’s lower
limit for frequency commands
nciMaxSpeed SNVT_lev_percent 100%
d2-01 Configures the maximum motor speed as a percentage of nciNmlFreq Sets the drive’s upper
limit for frequency commands
nciRampUpTm SNVT_time_sec 10sec C1-01 Configures motor ramp up time from 0 to its operating setpoint Sets the drive’s output
acceleration rate
nciRampDownTm SNVT_time_sec 10sec
C1-02 Configures motor ramp down time from its operating setpoint to 0 Sets the drive’s output
deceleration rate
nciSndHrtBt SNVT_time_sec
0sec
(off) n/a Configures the maximum period of time that expires before automatic propagation of
nvoDrvCurnt nvoDrvSpeed nvoDrvVolt and nvoDrvPwr
nciRcvHrtBt SNVT_time_sec
0sec
(off) n/a Configures the maximum period of time that expires between network variable updates
before a cable loss condition is declared and the drive is stopped
nciMinOutTm SNVT_time_sec 1sec
n/a Configures the minimum period of time that expires before changes in output network
variables are propagated
nciLocation
SNVT_str_asc
All “\0”
n/a
Available for a description of the physical location of the node
nciDrvSpeedScale SNVT_lev_percent
100%
n/a
Scales the speed setpoint nviDrvSpeedStpt (saved configured value)
nciOpModeRun
SNVT_count
1
b1-02
Selects the source for start/stop and speed commands
nciDrvMaxFreq SNVT_freq_hz 60.0Hz E1-04 Reports
the maximum output frequency of the drive (read-only)
nciMtrFLA SNVT_amp *
E2-01
Sets the full load current rating of the motor
nciPLRideThru
SNVT_count
2.0sec
L2-02
Selects the drive’s response to momentary power loss ride through time
nciAutoRstrt
SNVT_count
0
L5-01
Selects the number of times the drive attempts to automatically restart after certain faults
nciProFreq1
SNVT_freq_hz
0Hz
d3-01
Sets the center frequency for the first band of prohibit frequencies
nciProFreq2
SNVT_freq_hz
0Hz
d3-02
Sets the center frequency for the second band of prohibit frequencies
nciProFreqBW SNVT_freq_hz 1.0Hz d3-04
Sets the bandwidth for prohibit frequencies
nciPIDSel
SNVT_count
0
b5-01
Selects the mode of the PID controller
nciPID_PGain SNVT_multiplier 20
b5-02 Sets
the proportional gain of the PID controller
nciPID_ITime SNVT_time_sec 5.0sec b5-03
Sets
the
integral time constant of the PID controller
nvoDrvRatedCur SNVT_amp
*
n9-01
Reports the output current rating of the drive (read-only)
nciStallLevAcc SNVT_count *
L3-02
Sets the stall level for output current during acceleration
nciStallLevRun SNVT_count *
L3-06
Sets the stall level for output current while at set speed
nciCblLossSpeed SNVT_lev_percent 0%
n/a
Sets
speed level commanded if network communication is lost
nciCblLossFltEna SNVT_switch Off
n/a Enables
an
EF0 fault to be declared if network communication is lost
nciOpModeFreqRef SNVT_count
1
b1-01 Selects frequency reference source
* - Value dependent on drive capacity. Refer to appropriate Parameter Access and/or Technical Manual.