Vfd object network variable summary, Application overview 2-5 – Yaskawa LonWorks Option Card CM048 User Manual
Page 23
Application Overview 2-5
VFD Object Network Variable Summary
Table 2.3 - VFD Object Network Variable Summary
Index
Variable Name
Variable Type
Description
nv1
nviDrvSpeedStpt
SNVT_switch
Controls start/stop and a low resolution speed setpoint as a percentage of nciNmlFreq
nv2
nviDrvSpeedScale
SNVT_lev_percent Controls scaling for nviDrvSpeedStpt Negative values indicate reverse motor direction
nv3
nvoDrvCurnt
SNVT_amp
Reports output current
nv4 nvoDrvSpeed
SNVT_lev_percent
Reports
output
speed as a percentage of nciNmlFreq
nv5
nvoDrvVolt
SNVT_volt
Reports AC output voltage
nv6
nvoDrvPwr
SNVT_power_kilo Reports output power
nv7 nvoDrvRunHours
SNVT_time_hour
Reports accumulated run time
nv8 nviOpCommands SNVT_state
Controls the following operational commands:
bit 0 - External Fault (EF0)
bit 1 - Fault Reset
bit 2 - Multifunction Input 1 (terminal S3)
bit 3 - Multifunction Input 2 (terminal S4)
bit 4 - Multifunction Input 3 (terminal S5)
bit 5 - Multifunction Input 4 (terminal S6)
bit 6 - Multifunction Input 5 (terminal S7)
bit 7 - Reserved
nv9 nviReadParamNum SNVT_count
Requests a read of the specified drive parameter The response value is reported in
nvoReadParamVal
nv10 nviWriteParamNum SNVT_count
Requests a write of the specified drive parameter The write value is contained in
nviWriteParamVal
nv11
nviWriteParamVal
SNVT_count
Contains the value to be written to the drive parameter specified in nviWriteParamNum
nv12 nvoDrvStatus SNVT_state
Reports drive operational status:
bit 0 - Drive Running
bit 1 - Reverse Run Commanded
bit 2 - Drive Ready
bit 3 - Drive Faulted
bit 4 – Parameter Access Error
bit 5 – Multi-function Output 1
bit 6 – Multi-function Output 2
bit 7 – Reserved
bit 8 - Terminal S1 State
bit 9 - Terminal S2 State
bit 10 - Terminal S3 State
bit 11 - Terminal S4 State
bit 12 - Terminal S5 State
bit 13 - Terminal S6 State
bit 14 - Terminal S7 State
bit 15 - Reserved
nv13 nvoFltStatus SNVT_state
Reports drive fault status:
bit 0 - Overcurrent Ground Short Circuit
bit 1 - Overvoltage
bit 2 - Drive Overload
bit 3 - Overheat
bit 4 – Reserved
bit 5 – Fuse Blown
bit 6 – PID Feedback Lost
bit 7 - External Fault
bit 8 - Hardware Fault
bit 9 - Overload/Overtorque Fault
bit 10 – Excessive Speed Deviation
bit 11 - Undervoltage Fault
bit 12 – Undervoltage/Power Loss Fault
bit 13 – Input/Output Phase Loss
bit 14 – Drive Communication Loss
bit 15 – Operator Error