Option leds, Verify lonworks option operation, Installation 1-11 – Yaskawa LonWorks Option Card CM048 User Manual
Page 17
![background image](https://www.manualsdir.com/files/819867/content/doc017.png)
Installation 1-11
Option LEDs
The L
ON
W
ORKS
Option Unit is equipped with four indication LEDs for module and L
ON
W
ORKS
status indication. The LEDs are located on the
unit according to the figure below.
Figure 1.7 – L
ON
W
ORKS
LED Locations
Verify LonWorks Option Operation
Apply power to the drive.
Verify that the diagnostic LEDs on the front of the L
ON
W
ORKS
Option are in their correct state.
Table 1.3 – LED Status
LED Display
PWR Receive Transmit Fault
Service
Condition
Solution
BLINK
0.5Hz
Option is Not Configured
z
Configure Option
FLASH
1sON_2sOFF_ContON
Application missing
z
Download application image file
z
Assign network Identity
OFF
OFF
OFF
OFF
OFF
Power not supplied
z
Check that drive has power
z
Check option card seating in CN2 connector
ON BLINK BLINK
BLINK
OFF
Communications not
established
z
Check drive parameters (refer to table above)
z
Check connection between option and drive
ON
ON
OFF
Communications
Loss z
Check network cable connections
ON FLASH
OFF
OFF
Normal
communications
z
Flash each time serial task is complete
z
approximately 0.5Hz when drive is at STOP
z
approximately 1.0Hz when drive RUN is active
ON
FLASH
OFF
OFF
Normal
communications
z
Flash for every 5 network variables updates
Remove power from the drive and wait for the charge lamp to be completely extinguished. Wait at least five additional minutes for the
drive to be completely discharged. Measure the DC BUS voltage and verify that it is at a safe level.
Install the operator keypad and all drive covers.