Installation 1-10
Set Drive Parameters
Remove power from the drive and wait for the charge lamp to be completely extinguished. Wait at least five additional minutes for the
drive to be completely discharged. Measure the DC BUS voltage and verify that it is at a safe level.
Reinstall the operator keypad and all drive covers. Apply power to the drive.
Set parameter A1-01 to 2, Advanced.
Set parameters b1-01 and b1-02 to their appropriate values. Refer to the table below for available b1-01 and b1-02 values. Reference
Selection and Operation Method Selection can have different values depending on the application. To control both frequency and
run/stop over the network, set both b1-01 and b1-02 to 2, Serial Communications.
Set parameter H5-01 to 1Fh (31dec)
Set parameter H5-02 to 3, 9600 baud
Set parameter H5-03 to 0, No Parity
Set parameter H5-06 to 5, 5ms transmission wait
Set parameter H5-07 to 0, Disabled
Set parameter H5-08 to 0, MODBUS
Parameters H5-04 (Stopping Method at Communications Fault), H5-05 (Serial Fault Detection) and H5-09 (CE Detect Time) should
be set according to the desired drive performance during a communications timeout or failure.
After all drive parameters have been set, power cycle the drive. Communications parameters will not take affect until power has been
removed from the drive until the charge lamp has been extinguished and restored.
If any of these settings is incorrect, “CALL” will blink on the digital operator, as will the RECEIVE, TRANSMIT and FAULT
LEDs on the L
ON
W
ORKS
Option. This is an indication that the drive has not yet established communication with the option card. Once
the drive has properly exchanged messages with the option card, “CALL”.will no longer be displayed on the digital operator.
For By-Pass applications, refer to the parameter table accompanying the by-pass unit for parameter settings.
Table 1.2 – Drive Parameter Settings
Parameter
Function
Data
+/- Limits - Description
Default
0 Operator
1 User
A1-01 Access
Level
2 Advanced
2
0 Digital
Operator
1 Terminals
2
Serial Communication (LonWorks)
3 Option
PCB
b1-01 Reference
Selection
4
Pulse Input (F7 and G7 Drives only)
1
0 Digital
Operator
1 Terminals
2
Serial Communication (LonWorks)
b1-02 Operation
Method
Selection
3 Option
PCB
1
H5-01 Serial
Communications
Address
1F
0 – 1Fh (0 – 31 dec)
1Fh
0 1200
baud
1 2400
baud
2 4800
baud
3
9600 baud (LonWorks)
H5-02
Serial Baud Rate Select
4 19200
baud
3
0 None
(LonWorks)
1 Even
parity
H5-03
Serial Parity Select
2 Odd
parity
0
H5-06
Transmit Wait
5
5 – 65ms
5
0 Disabled
(LonWorks)
H5-07
RTS Control Select
1 Enabled
0
0 MODBUS
(LonWorks)
1
N2 (Metasys) (E7, E7B and E7L only)
H5-08 Protocol
Select
2
P1 (APOGEE) (E7, E7B and E7L only)
0