Parameter access errors, Application overview 2-6 – Yaskawa LonWorks Option Card CM048 User Manual
Page 24
Application Overview 2-6
Table 2.3 - VFD Object Network Variable Summary
Index
Variable Name
Variable Type
Description
nv14
nvoSpdStptFb
SNVT_lev_percent Reports the speed setpoint as a percentage of nciNmlFreq
nv15
nvoSpdCmd
SNVT_lev_percent Reports the speed command as a percentage of nciNmlFreq regardless of command source
nv16
nvoPIDFb
SNVT_lev_percent Reports the PID feedback as a percentage of nciNmlFreq
nv17
nvoDrvBus
SNVT_volt
Reports DC Bus voltage
nv18 nvoReadParamVal SNVT_count
Reports
value of requested parameter
nv19
nviDrvFltRst
SNVT_switch
Resets a drive fault
nv20
nvoRunStp
SNVT_switch
Reports the Run/Stop status of the drive
nv21 nvoDrvFlt SNVT_switch
Reports drive fault condition
nv22
nvoDrvParamErr
SNVT_count
Reports parameter access error
nv23
nvoDrvTemp
SNVT_temp
Reports drive temperature
nv24
nvoDrvEnergyKwh
SNVT_elec_kwh Reports cumulative energy in kWh
nv25
nvoDrvEnergyMwh
SNVT_elec_kwh Reports cumulative energy in mWh
Parameter Access Errors
These values are returned by nv22 when a communications error occurres.
0 -
Normal
2 -
Incorrect register error
33 - Data range error
34 - Parameter not writable in Run mode
35 – Write when drive is in Undervoltage
36 – Process busy
255 - Command timeout error