Drive Faults

The following is a table of faults that could be caused by the L

ON

W

ORKS

Option that will be displayed on the Operator Keypad, their causes, and

possible solutions. For any fault displayed on the operator that is not listed in the following table, please see the appropriate drive technical

manual.

Table 1.4 – Drive Faults

Fault

Content

Cause

Solution

BUS

Option PCB communications error

Communication is not established between

L

ON

W

ORKS

Master and the drive.

z

Check L

ON

W

ORKS

communication LED display.

EF0

Option PCB external fault

Drive received an external fault command
from the Option PCB

z

Check multi-function input settings

z

Check PLC or controller program

z

Eliminate cause of fault (machine device in fault state)

OPE05

Command selection fault

Parameter b1-01 is set to Option PCB and no
card is detected

z

Install Option PCB

z

Reprogram b1-01

z

Replace the Option PCB

OPE06

Control mode selection fault

Parameter b1-02 is set to Option PCB and no

card is detected

z

Install Option PCB

z

Reprogram b1-02

z

Replace the Option PCB