5. Bypass Applications
For many applications, the drive is integrated into a bypass or engineered package. This type of
package typically features an enclosure with contactors which allow the user to run the motor from line
power (bypass mode) or from the drive (drive mode). This package also provides the flexibility for
interfacing normally closed safety interlocks (firestat, freezestat, vibration sensors, etc.) which stop the
drive if the contacts open.
5.1 Typical Parameter Settings
Because of the widespread use of this type of application, the following parameter set-up table is
provided to aid in the start-up of such a drive.
GPD505
Parameter
GPD505
Setting
GPD506/P5
Parameter
GPD506/P5
Setting
Description
n001
3
n001
3
Enables Parameter Write Access
n002
6
n002
6
Operational Mode (Network Control)
n006
1
n006
1
Reverse Run Disabled
n007
0
n007
0
Local/Remote Button Disabled
n019
60
n018
60
Accel Time (secs)
n020
60
n019
60
Decel Time (secs)
n025
10
n024
10
Initial Reference (Hz)
n026
6
n025
6
Alternate Reference (Hz)
n037
5
n038
5
Terminal S4 Select - Local/Remote
n038
9
n039
10
Terminal S5 Select - Manual Speed
n039
19
n040
21
Terminal S6 Select - PID Disable
n051
1
n055
1
Momentary Power Loss
n064
50
n068
50
DC Injection Braking Level (%)
n066
5
n070
5
DC Injection Time at Start (sec)
n103
1
n101
1
Modbus Timeout Enabled
n104
0
n102
0
Ramp to Stop on Modbus Timeout