21

5. Bypass Applications

For many applications, the drive is integrated into a bypass or engineered package. This type of
package typically features an enclosure with contactors which allow the user to run the motor from line
power (bypass mode) or from the drive (drive mode). This package also provides the flexibility for
interfacing normally closed safety interlocks (firestat, freezestat, vibration sensors, etc.) which stop the
drive if the contacts open.

5.1 Typical Parameter Settings

Because of the widespread use of this type of application, the following parameter set-up table is
provided to aid in the start-up of such a drive.

GPD505

Parameter

GPD505

Setting

GPD506/P5

Parameter

GPD506/P5

Setting

Description

n001

3

n001

3

Enables Parameter Write Access

n002

6

n002

6

Operational Mode (Network Control)

n006

1

n006

1

Reverse Run Disabled

n007

0

n007

0

Local/Remote Button Disabled

n019

60

n018

60

Accel Time (secs)

n020

60

n019

60

Decel Time (secs)

n025

10

n024

10

Initial Reference (Hz)

n026

6

n025

6

Alternate Reference (Hz)

n037

5

n038

5

Terminal S4 Select - Local/Remote

n038

9

n039

10

Terminal S5 Select - Manual Speed

n039

19

n040

21

Terminal S6 Select - PID Disable

n051

1

n055

1

Momentary Power Loss

n064

50

n068

50

DC Injection Braking Level (%)

n066

5

n070

5

DC Injection Time at Start (sec)

n103

1

n101

1

Modbus Timeout Enabled

n104

0

n102

0

Ramp to Stop on Modbus Timeout