11
Point #
Database
Descriptor
Point
Type
Units
(SI)
Slope
Interce
pt
On Text
Off Text
Default
{39}
FREQ LOW LM
LAO
PCT
1.0
0
--
--
0
{40}
MULTI OUT 1
LDI
--
--
--
ON
OFF
OFF
{41}
MULTI OUT 2
LDI
--
--
--
ON
OFF
OFF
{42}
TERM S1 MON
LDI
--
--
-
CLOSED
OPEN
OPEN
{43}
TERM S2 MON
LDI
--
--
-
CLOSED
OPEN
OPEN
{44}
TERM S3 MON
LDI
--
--
-
CLOSED
OPEN
OPEN
{45}
TERM S4 MON
LDI
--
--
-
CLOSED
OPEN
OPEN
{46}
TERM S5 MON
LDI
--
--
-
CLOSED
OPEN
OPEN
{47}
TERM S6 MON
LDI
--
--
-
CLOSED
OPEN
OPEN
{55}
OP MODE SEL
LAO
--
1.0
0
--
--
6
{60} FREQ
REF LAO HZ 0.1 0 -- -- 0
{61}
FREQ REF MON
LAI
HZ
0.1
0
--
--
0
{62} PID
FEEDBACK LAI HZ 0.1
0
--
--
0
{63} PI
GAIN LAO
-- 0.1 0 -- -- 1.0
{64} PI
TIME LAO
SEC
0.1
0 -- -- 10.0
(65} PID
SELECT LAO -- 1.0 0 --
--
0
{70}
RD PARAM NUM
LAO
--
1.0
0
--
--
0
{71}
RD PARAM DAT
LAI
--
1.0
0
--
--
0
{72}
WR PARAM NUM
LAO
--
1.0
0
--
--
0
{73}
WR PARAM DAT
LAO
--
1.0
0
--
--
0
{80}
S1 RUN ILOCK
LDO
--
1.0
0
ENABLE
DISABL
ENABLE
{81}
S5 AUTO RUN
LDO
--
1.0
0
ENABLE
DISABL
ENABLE
{90}
CBL LOSS FLT
LDO
--
1.0
0
ENABLE
DISABL
DISABL
{91}
CBL LOSS FRQ
LAO
HZ
0.1
0
--
--
0
{92}
CBL LOSS TMR
LAO
SEC
0.1
0
--
--
0
{93}
FAULT
LDI
--
--
--
FAULT
NO FLT
NO FLT
{94}
FAULT RESET
LDO
--
--
--
RST ON
RSTOFF
RSTOFF
{96}
EXTERNAL FLT
LDO
--
--
--
FLT ON
FLTOFF
FLTOFF
Notes
1. Slope is dependent on drive capacity. For drives with a rated current of 180 A or less, the slope is