3 drive monitoring, 1 operating status – Yaskawa GPD506/P5 with Apogee FLN Option User Manual
Page 17
16
4.3 Drive Monitoring
This section describes the logical points used to monitor the drive. Refer to the appropriate Technical
Manual for additional information.
4.3.1 Operating Status
The following table summarizes the input points available for monitoring the operating status of the drive.
Operating Variable
Point #
Description
Output Frequency
3
Reports output frequency in Hz.
Output Percentage
4
Reports operating output as a percentage of maximum output frequency.
Output Speed
5
Reports output speed in RPM (4-pole motor).
Output Current
6
Reports output current.
Output Power
8
Reports output power. This point is only available on GPD506/P5 drives.
Drive Temperature
9
Reports drive temperature. This point is only available on GPD506/P5 drives.
Kilowatt Hour Meter
10
Reports cumulative drive energy usage in kilowatts. This point is only available
on GPD506/P5 drives.
Megawatt Hour Meter
11
Reports cumulative drive energy usage in megawatts. This point is only
available on GPD506/P5 drives.
DC Bus Voltage
13
Reports DC bus voltage.
AC Output Voltage
14
Reports AC output voltage (i.e. voltage applied to motor).
Elapsed Timer – Hrs
15
Reports cumulative run time in hours.
Elapsed Timer – 10K Hrs
16
Reports cumulative run time in increments of 10K hours.
Fault Code
17
Reports drive fault status. This value is the decimal equivalent of a binary fault
word. It is the sum of the values associated with each fault bit, as listed below:
Fault
Bit Value
Overcurrent, Ground, Short Circuit
0
1
Overvoltage
1 2
Drive
Overload
2 4
Overheat
3 8
Main
Circuit
5 32
Brake
Transistor
6 64
External
7 128
Hardware
8 256
Motor
Overload
9 512
During Undervoltage
11
2048
Power Loss
12
4096
Phase
13
8192
Forward/Reverse Status
21
Reports the forward/reverse status (1=Reverse) as commanded from the source
selected by #55 (operator, terminal, or network). This allows the status to be
monitored even when the network is not the command source.
This value matches #22 only when the network is selected as the command
source (#55 = 6,7,8).
Run Status
23
Reports the run status (1=Run) as commanded from the source selected by #55
(operator, terminal, or network). This allows the status to be monitored even when
the network is not the command source.
This value matches #24 only when the network is selected as the command
source (#55 = 6,7,8).
Multifunction Output 1
25
Reports the status of Multifunction Output 1 (1=On). The function assigned to this
output is programmed in GPD505 parameter n040 or GPD506/P5 parameter
n041.
Multifunction Output 2
26
Reports the status of Multifunction Output 2 (1=On). The function assigned to this
output is programmed in GPD505 parameter n041 or GPD506/P5 parameter
n042.
Drive Ready Status
35
Reports whether or not the drive is ready to accept a run command (1=Ready).
Terminal S1 Monitor
42
Reports the status of Terminal S1 (1=Closed).
Terminal S2 Monitor
43
Reports the status of Terminal S2 (1=Closed).
Terminal S3 Monitor
44
Reports the status of Terminal S3 (1=Closed).
Terminal S4 Monitor
45
Reports the status of Terminal S4 (1=Closed).
Terminal S5 Monitor
46
Reports the status of Terminal S5 (1=Closed).
Terminal S6 Monitor
47
Reports the status of Terminal S6 (1=Closed).
Frequency Reference
61
Reports the frequency reference as commanded from the source selected by #55
(operator, terminal, or network). This allows frequency reference to be monitored