2 logical analog output (lao) summary, 3 logical digital input (ldi) summary, 4 logical digital output (ldo) summary – Yaskawa GPD506/P5 with Apogee FLN Option User Manual
Page 10

9
3.2 Logical Analog Output (LAO) Summary
Point Description
Point #
GPD505
Parameter
GPD506/P5
Parameter
Units
(SI)
Slope Intercept
Default Min Max
Override
Time 20 n/a n/a
Hrs
1.0 0 8 1 12
Acceleration Time
31
n019
n018
Sec
0.1
0
10.0
0
3276.7
Deceleration Time
32
n020
n019
Sec
0.1
0
10.0
0
3276.7
Freq Command Upper
Limit
38 n030 n031 % 1.0 0 100 0 109
Freq Command Lower
Limit
39 n031 n032 % 1.0 0 0 0 100
Operational Mode
Select
55
n002
n002
-
1.0 0 6 0 8
Frequency Command
60
n/a
n/a
Hz
0.1
0
0
0
Note 1
PID Proportional Gain
63
n086
n086
-
0.1
0
1.0
0.0
10.0
PID Integral Time
64
n087
n087
Sec
0.1
0
10.0
0.0
100.0
PID Mode Select
65
n084
n084
-
1.0
0
0
0
3
Read Parameter
Number
70 n/a n/a -
1.0 0 0 1 114
Write Parameter
Number
72 n/a n/a -
1.0 0 0 1 114
Write Parameter Data
73
n/a
n/a
-
1.0
0
0
0
9999
Cable Loss Frequency
91
n/a
n/a
Hz
0.1
0
0
0
Note 1
Cable Loss Timeout
92
n/a
n/a
Sec
0.1
0
0
0
3276.7
Notes
1. Value dependent on maximum output frequency of the drive. Default is 60.0 Hz.
3.3 Logical Digital Input (LDI) Summary
Point Description
Point #
Off (0)
State
On (1)
State
Forward/Reverse Monitor
21
Forward
Reverse
Run/Stop Monitor
23
Stopped
Running
Drive Ready Monitor
35
Not Ready
Ready
Multifunction Output 1
40
Note 1
Note 1
Multifunction Output 2
41
Note 1
Note 1
Terminal S1 Monitor
42
Open
Closed
Terminal S2 Monitor
43
Open
Closed
Terminal S3 Monitor
44
Open
Closed
Terminal S4 Monitor
45
Open
Closed
Terminal S5 Monitor
46
Open
Closed
Terminal S6 Monitor
47
Open
Closed
Fault Monitor
93
Not Faulted
Faulted
Notes
1. States are dependent on the setup of the Multifunction Outputs. Refer to appropriate Technical
Manual.
3.4 Logical Digital Output (LDO) Summary
Point Description
Point #
Off (0)
State
On (1)
State
Default
Forward/Reverse
Command
22 Forward
Reverse Off
Run/Stop Command
24
Stop
Run
Off
Terminal S3 Command
25
Open ( See Note 1 )
Closed ( See Note 1 )
Off
Terminal S4 Command
26
Open ( See Note 1 )
Closed ( See Note 1 )
Off
Terminal S5 Command
27
Open ( See Note 1 )
Closed ( See Note 1 )
Off
Terminal S6 Command
28
Open ( See Note 1 )
Closed ( See Note 1 )
Off
Day/Night Mode Selection
29
Day Mode
Night Mode
Off